LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

 

 

 

Table 5. Power Factor By Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Of Load

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 120

 

At 240

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

 

Volts

 

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

 

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

 

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

 

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

 

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

 

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

 

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load output maybe determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

PAGE 24 — DCA25USIXF/DCA25USI2XF — OPERATION AND PARTS MANUAL — REV. #2 (07/26/11)

Page 24
Image 24
Multiquip DCA25USIXF, DCA25USI2XF operation manual Load Application, Single Phase Load, Three Phase Load

DCA25USI2XF, DCA25USIXF specifications

Multiquip is a renowned name in the construction and industrial equipment sector, known for delivering high-performance generators that cater to various power needs. Two standout models in their lineup are the DCA25USIXF and DCA25USI2XF, both designed for reliability, efficiency, and versatility.

The Multiquip DCA25USIXF is a compact, industrial-grade diesel generator that delivers a powerful 25 kVA, making it ideal for construction sites, outdoor events, and emergency backup applications. This model is powered by a robust Yanmar diesel engine, which ensures high fuel efficiency and low emissions, adhering to stringent environmental standards. The DCA25USIXF features an advanced digital control panel, providing users with an intuitive interface for monitoring performance, voltage output, and operational status. Its sound-attenuated enclosure significantly reduces noise levels, making it suitable for use in noise-sensitive areas.

On the other hand, the DCA25USI2XF model takes power generation a step further by offering dual voltage capabilities, allowing users to switch between 120V and 240V outputs. This flexibility makes it highly versatile, catering to a broader range of tools and equipment. Like the DCA25USIXF, the DCA25USI2XF is also equipped with Yanmar’s reliable diesel engine, which contributes to its durability and long service life. Both models come with a heavy-duty frame to withstand tough conditions, ensuring durability on job sites.

The technology implemented in these generators includes automatic voltage regulation (AVR), which stabilizes voltage output, protecting sensitive equipment from power surges. Additionally, the generators feature a low oil shutdown system, which prevents engine damage by automatically shutting down the generator when oil levels are low. This protective measure not only enhances the longevity of the generator but also contributes to safer operation.

In terms of portability, both models are equipped with rugged wheels and a lifting eye, facilitating easy transportation to various job sites. With their combination of power, efficiency, and advanced features, the Multiquip DCA25USIXF and DCA25USI2XF generators are excellent choices for professionals seeking reliable power solutions in demanding environments. Whether for construction, events, or standby power, these generators deliver exceptional performance tailored to meet diverse needs.