Multiquip DCA25USIXF Shutdown, Normal Shut-down Procedure, Emergency Shut-down Procedure

Models: DCA25USI2XF DCA25USIXF

1 98
Download 98 pages 10.97 Kb
Page 36
Image 36
SHUTDOWN

SHUTDOWN

Normal Shut-down Procedure

To shutdown the generator, use the following procedure:

1.Switch the MAIN, AUX and GFCI circuit breakers (Figure 53) to the OFF position (no load).

Emergency Shut-down Procedure

1.To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 53) circuit breakers to OFF position.

2.Turn the ignition switch key to the STOP position (Figure 54).

Automatic Shut-down System

This unit is equipped with safety devices to automatically stop the engine in the event of low oil pressure, approximately 14 psi (97 kPa), or high water temperature, approximately 230° F (110° C). The alarm lamps on the Engine Control Panel illuminate to signify the reason for the shutdown.

Figure 53. Main, AUX. and GFCI

Circuit Breakers (OFF)

3.Let the engine cool by running it for 3-5 minutes with no load applied (circuit breakers in the OFF position).

4.Place the ignition switch (Figure 54) in the “STOP”position, remove the key and store in a safe place.

CAUTION

After automatic shut-down, ALWAYS inspect the unit and eliminate any problems before attempting to restart. Failure to do so can damage the unit.

Before inspecting, turn the starter switch to the STOP position, place all Generator Circuit Breakers in the OFF position and allow sufficient time for adequate cooling. When ready to restart, complete all steps in the Generator Startup Procedure section of this manual.

Figure 54. Ignition Switch (Off Position)

5.Remove all loads from the generator.

6.Allow for sufficient time for cooling and then inspect the complete unit for any damage or loosening that may have occured during operation.

7.Check the engine oil, coolant and fuel levels. Replenish as necessary.

NOTICE

Engine protection is furnished during operation, but cannot replace normal preventive maintenance.

Regularly maintain the unit as specified in the Maintenance section of this manual to prevent damage.

PAGE 36 — DCA25USIXF/DCA25USI2XF — OPERATION AND PARTS MANUAL — REV. #2 (07/26/11)

Page 36
Image 36
Multiquip DCA25USIXF Shutdown, Normal Shut-down Procedure, Emergency Shut-down Procedure, Automatic Shut-down System