14.3 Startup Procedures

The procedure to start the UPS is shown in Steps 1-5.

LED Key

 

 

 

 

 

 

 

 

- LED Off

 

 

 

 

 

 

 

 

- LED On

 

 

 

 

 

 

 

 

- LED Flash

STEP 1

Turn on the control power supply switch. (Figure 14.1) and ensure the operation lock is set to OPERATION. (Figure 13.1 - 1)

AC INPUT

BATTERIES

BYPASS INPUT

SYSTEM INITIALIZE

 

UPS

CONVERTER

INVERTER

FLOAT CHARGE

AC

EQUAL CHARGE

DISCHARGE

SWITCH

BYPASS

AC OUTPUT

STEP 2

Wait for a few seconds.

AC INPUT

BATTERIES

BYPASS INPUT

BYPASS

PRESS ‘RUN’ SWITCH

 

UPS

CONVERTER

INVERTER

FLOAT CHARGE

AC

EQUAL CHARGE

DISCHARGE

SWITCH

BYPASS

AC OUTPUT

STEP 3

Press the “RUN” button for at least 0.5 seconds.

CONVERTER LED is “ON” and INVERTER LED flashes.

AC INPUT

BATTERIES

BYPASS INPUT

BYPASS

UPS STARTING

WAIT FOR A WHILE

 

UPS

 

CONVERTER

INVERTER

 

FLOAT CHARGE

AC

 

EQUAL CHARGE

 

DISCHARGE

SWITCH

AC OUTPUT

 

BYPASS

56

G8000 Series Installation and Operation Manual

Page 64
Image 64
Toshiba G8000 operation manual Startup Procedures, Procedure to start the UPS is shown in Steps