14.5Stop

The procedure to stop the UPS is shown in Steps 1-3.

LED Key

- LED Off

- LED On

- LED Flash

BYPASS

AC - Vo 480 V

AC - Io 50%

PRESS ‘UPS’ SWITCH

STEP 1

Transfer to Bypass supply as described in Switch Power Supply.

UPS LED is “OFF”.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

 

SWITCH

AC OUTPUT

 

BYPASS

 

BYPASS LED is “ON”.

BYPASS

MOVE #72B TO ‘OFF’ POSITION

STEP 2

Turn off the DC Input Breaker (72B) on the external battery cabinet, and, press the G8000 “STOP” button for at least 0.5 seconds.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

INVERTER

UPS

AC

 

SWITCH

AC OUTPUT

 

BYPASS

 

BATTERIES LED is “OFF”.

INVERTER LED flashes then “OFF”.

FLOAT CHARGE LED and CONVERTER LED are “OFF”.

AC INPUT

BATTERIES

BYPASS INPUT

BYPASS

PRESS ‘RUN’ SWITCH

 

UPS

 

CONVERTER

INVERTER

 

FLOAT CHARGE

AC

 

EQUAL CHARGE

 

DISCHARGE

SWITCH

AC OUTPUT

 

BYPASS

STEP 3

Wait until procedure is completed.

G8000 Series Installation and Operation Manual

59

Page 67
Image 67
Toshiba G8000 operation manual Stop