14.4Switch Power Supply (UPS→Bypass)
The procedure to transfer between the UPS supply and the bypass supply is shown in Steps
LED Key
- LED Off
- LED On
- LED Flash
STEP 1
Check AC INPUT LED and BYPASS LED are on to make sure power is being delivered to the UPS.
AC INPUT
BATTERIES
BYPASS INPUT
UPS SUPPLY
AC - Vo 480 v
AC - Io 50%
| UPS |
|
CONVERTER | INVERTER |
|
FLOAT CHARGE | AC |
|
EQUAL CHARGE |
| |
DISCHARGE | SWITCH | AC OUTPUT |
|
BYPASS
STEP 2
Press the “BYPASS” button for at least 0.5 seconds.
UPS LED is “OFF”.
BYPASS
BYPASS LED is “ON”.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
UPS
INVERTER
AC |
|
SWITCH | AC OUTPUT |
| |
BYPASS |
|
STEP 3
Please wait until procedure is completed.
Note
To change from Bypass to UPS supply, follow the Startup Procedures - STEP 5.
If the AC switch does not function, contact Toshiba or authorized representatives.
AC INPUT
BATTERIES
BYPASS INPUT
BYPASS
AC - Vo 480 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
| UPS |
|
CONVERTER | INVERTER |
|
FLOAT CHARGE | AC |
|
EQUAL CHARGE |
| |
DISCHARGE | SWITCH | AC OUTPUT |
|
BYPASS
58 | G8000 Series Installation and Operation Manual |