14.4Switch Power Supply (UPS→Bypass)

The procedure to transfer between the UPS supply and the bypass supply is shown in Steps 1-3

LED Key

- LED Off

- LED On

- LED Flash

STEP 1

Check AC INPUT LED and BYPASS LED are on to make sure power is being delivered to the UPS.

AC INPUT

BATTERIES

BYPASS INPUT

UPS SUPPLY

AC - Vo 480 v

AC - Io 50%

 

UPS

 

CONVERTER

INVERTER

 

FLOAT CHARGE

AC

 

EQUAL CHARGE

 

DISCHARGE

SWITCH

AC OUTPUT

 

BYPASS

STEP 2

Press the “BYPASS” button for at least 0.5 seconds.

UPS LED is “OFF”.

BYPASS

BYPASS LED is “ON”.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

 

SWITCH

AC OUTPUT

 

BYPASS

 

STEP 3

Please wait until procedure is completed.

Note

To change from Bypass to UPS supply, follow the Startup Procedures - STEP 5.

If the AC switch does not function, contact Toshiba or authorized representatives.

AC INPUT

BATTERIES

BYPASS INPUT

BYPASS

AC - Vo 480 V

AC - Io 50%

PRESS ‘UPS’ SWITCH

 

UPS

 

CONVERTER

INVERTER

 

FLOAT CHARGE

AC

 

EQUAL CHARGE

 

DISCHARGE

SWITCH

AC OUTPUT

 

BYPASS

58

G8000 Series Installation and Operation Manual