11.5Grounding Configuration

This section describes the grounding configuration to be used with various AC service entrance configurations.

Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral line must be made appropriately according to the system configuration.

11.5.1Recommended configuration (for 4 wire input with Input Neutral grounded)

Figure 11.11 shows recommended grounding configuration when the input neutral is grounded.

The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be disconnected from the ground bus. The neutral connection for the UPS bypass input should be grounded.

Input Source

 

< UpS Cabinet >

 

 

3

3

 

 

N

 

N

3

 

3

3

 

 

 

N

G

G

G

3

N

To the

G

load

 

remove

Jumper Cable

FIGURE 11.11 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED

A 2 AWG (or 38mm2) jumper cable is provided between the neutral terminal and ground bus in the UPS cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable location is illustrated below.

100-225 kVA

 

 

 

 

 

300 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

Ground

Ground

Terminal

 

 

 

 

Bus

Bus

 

 

 

 

Remove

 

 

 

 

 

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

Terminal

Remove

Jumper

Cable

FIGURE 11.12 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS

40

G8000 Series Installation and Operation Manual

Page 48
Image 48
Toshiba G8000 operation manual Grounding Configuration with Input Neutral Grounded