The terminal busses for the 300 kVA UPS are located inside at the top of the unit. See Figure 11.6. The dashed line indicates the side view of the bolt holes. Use 1/2 inch bolts to attach the lugs.

See Tables 11.5 for recommended cable size for the 300 kVA UPS. See Table 11.4 and Table 11.6 for vendor recommended lugs.

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

 

10

11

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U

V

W

-

+

U

V

w

N

U

V

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC INPUT

 

BATTERY

 

BYPASS INPUT

 

AC OUTPUT

 

3-phase 3-wire

 

 

 

 

 

3-phase 4-wire

 

3-phase 4-wire

 

FIGURE 11.7 - TERMINAL BUSSES OF THE 300 kVA UPS

Figure 11.7 shows the four (4) cable knockout plates provided at the top of the 300 kVA UPS. Seven (7) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the knockout plates.

plate #1

Plate #4

Plate #1

 

plate

2“ Dia.

plate #2

 

plate #3

2“ Dia.

1.5”

 

plate #2

 

Plate #3

0.4”

4” Dia.

 

 

 

 

 

 

 

 

 

0.6”

 

 

 

0.6”

 

GROUND WIRE

0.8”

-

+

CONTROL WIRES

 

 

 

 

 

AC INPUT

BATTERY

BYPASS AC OUTPUT

 

 

 

Figure 11.8 - CABLE KNOCKOUT PLATES (300 kVA

34

G8000 Series Installation and Operation Manual

Page 42
Image 42
Toshiba G8000 operation manual Plate #4