4.4Inspection/Storage
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original crating and packing materials for return to the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.
Storage
During periods of
Storage Preparation
1)Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.
2)Stop the unit.
3)Place the Main Circuit Breaker switch in the “OFF” position.
Storage Conditions
•For best results, store the UPS in the original shipping container and place on a wood or metal pallet
•Storage temperature range:
•The optimum storage temperature is 70 °F (21 °C). A higher ambient temperature will require recharging more frequently during storage
Avoid the following storage locations:
•Locations that are subject to extreme temperature changes or high humidity
•Locations that are subject to high levels of dust or metal particles
•Locations that are subject to excessive vibration
•Inclined floor surfaces
G8000 Series Installation and Operation Manual