12.2Mechanical Specification (cont.)

Rated Capacity

150 kVA

225 kVA

300 kVA

Cabinet

 

 

 

Protection

 

IEC298 IP20*

 

Conformity

 

 

 

Exterior Paint

Sherwin Williams, HHT2-7055, 079 Beige Texture

 

FRONT: 1/16 in. (1.6 mm)

Panel Thickness

BACK/SIDE/TOP: 3/64 in. (1.2 mm)

 

BOTTOM: 1/8 in. (3.2 mm)

Input/Output

TOP and BOTTOM

TOP

Cabling Entrance

 

 

 

Ground/Control

TOP and BOTTOM

TOP

Wiring Entrance

 

 

 

Clearance

 

 

 

 

 

 

W: 76.8 in.

 

W: 55.1 in. (1,400 mm)

(1,951 mm)

Outline

D: 31.8 in.

D: 31.8 in. (808 mm)

Dimension

(808 mm)

H: 79.2 in. (2,012 mm)

 

H: 79.4 in.

 

 

 

 

 

 

(2,017 mm)

Unit Weight

2,600 lbs (1,180 kg)

3,300 lbs (1,500 kg)

4,850 lbs (2,205 kg)

Shipping Weight

2,689 lbs (1,220 kg)

3,389 lbs (1,538 kg)

5,000 lbs (2,273 kg)

Floor Loading

3,280 lbs/ft2

4,134 lbs/ft2

2,608 lbs/ft2

Per Footprint

(16,014 kg/m2)

(20,184 kg/m2)

(12,733 kg/m2)

 

FRONT: 43 7/16 in. (1,100 mm)

Clearance

BACK/SIDE: 0 in. (0 mm)

 

TOP: 15 3/4 in. (400 mm)

Heat Rejection

35,635 BTU/h

46,268 BTU/h

61,690 BTU/h

(8,980 kcal/h)

(11,659 kcal/h)

(15,546 kcal/h)

 

*IP20: Foreign objects that are 12mm (15/32”) or larger are prevented from entering the enclosure of the UPS.