TABLE 11.5 RECOMMENDED CABLE SIZE AND TIGHTENING TORQUE FOR 300 kVA UPS

Bus Number

Cable Size

Tightening Torque

1

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

2

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

3

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

*4

Three 350 MCM or larger

275 in-lbs (3.2 kg-m)

*5

Three 350 MCM or larger

275 in-lbs (3.2 kg-m)

6

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m) )

7

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

8

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

9

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m) )

10

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

11

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

12

Two 4/0 AWG or larger

275 in-lbs (3.2 kg-m)

NOTE: Maximum cable size is 600MCM

*Two battery strings or more (consult factory if using one

battery string)

TABLE 11.6 RECOMMENDED LUGS for use with 300 kVA UPS

Terminal Bus #

 

Recommendation

 

Vendor

Catalog #

1

 

TA-600

2

ILSCO

AU-600

3

 

 

 

4

ILSCO

TA-600

5

T3A2-600N

 

6

 

TA-600

7

 

 

AU-600

8

 

 

 

9

ILSCO

TA-600, T3A2-600N

10

 

TA-600

11

 

 

AU-600

12

 

 

 

G8000 Series Installation and Operation Manual

35

Page 43
Image 43
Toshiba G8000 operation manual Bus Number Cable Size Tightening Torque, Terminal Bus # Recommendation