11.1Terminal Blocks and Power Cables
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit protection device requirements.
The terminal blocks for the 100/150/225 kVA UPS are shown in Figure 11.2. The terminal blocks are located inside, at the bottom of the UPS. If the UPS has terminal buses see Table 11.4 for lug recommendations.
Recommended external cable size and tightening torque for a single battery string are listed in Table
Use only copper wires for external cables.
| 1 | 2 | 3 | 4 | 5 | 6 |
| 7 | 8 | 9 | 10 |
| 11 |
| 12 | 13 |
| |||||||||
| 1 | 2 | 3 | 4 | 5 | 6 |
| 7 | 8 | 9 | 10 |
| 11 |
| 12 | 13 |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
U |
| V | W | U | V | W | N | U | V | w | N | - | + | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BATTERY | |||
|
| AC INPUT |
|
|
|
| BYPASS INPUT |
|
|
| AC OUTPUT |
|
| |||||||
|
|
|
|
| FIGURE 11.2 - TERMINAL BLOCKS OF 100/150/225 kVA UPS |
|
|
|
|
|
| |||||||||
|
|
| TABLE 11.1 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 100 kVA UPS |
|
| |||||||||||||||
|
|
| Block Number |
|
|
| Cable Size |
|
|
| Tightening Torque |
|
|
|
| |||||
|
|
|
| 1 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 2 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 3 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 4 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 5 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 6 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 7 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 8 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 9 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 10 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| 11 |
|
| AWG 1/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| *12 |
|
| TWO AWG 3/0 or larger |
|
| 275 |
|
|
|
| ||||||
|
|
|
| *13 |
|
| TWO AWG 3/0 or larger |
|
| 275 |
|
|
|
|
NOTE: Maximum cable size is AWG 2/0
*One battery string (see note, pg. 35, if using multiple battery strings)