If your system is equiped with bus strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.4, or their equivalent, for cable terminations for mounting on the bus strip.

5.3 in. (135 mm)

1.97 in.

1.77 in.

(50 mm)

(45 mm)

 

 

 

 

 

 

 

 

 

 

1.75 in.

(45 mm)

3in.

(77 mm)

FIGURE 11.6 - TERMINAL BUS Detail

table 11.4 Recommended crimp type compression lugs for Bus Strip Terminals

Wire Size

Wire

Recommendation

Crimp tool Required

 

Strand

 

 

Burndy type Y35 or Y46

 

Class

Vendor

Cat. No.

Color Key

Die Index

1/0

B

Burndy

YA25

Pink

12 / 348

 

I

Ilsco

CRA-1/OL

Pink

12 / 348

 

B

Burndy

YA25-LB

Black

13

2/0

B

Burndy

YA26

Black

13

 

I

Ilsco

CRA-2/OL

Black

13

 

B

Burndy

YA27-LB

Orange

14 / 101

3/0

B

Burndy

YA-27

Orange

14 / 101

 

I

Ilsco

CRB-3/OL

Orange

14 / 101

 

B

Burndy

YA28-LB

Purple

15

4/0

B

Burndy

YA28

Purple

15

 

I

Ilsco

CRB-4/OL

Purple

15

 

B

Burndy

YA29-LB

Yellow

16

300 MCM

B

Burndy

YA30

White

17 / 298

 

I

Ilsco

CRA-30OL

White

17 / 298

 

B

Burndy

YA32-LB

Red

18 / 324

350 MCM

B

Burndy

YA31L

Red

18

 

I

Ilsco

CRA-350

Red

18

600 MCM

B

Burndy

YA36L

Green

22

 

I

Ilsco

CRA-600

Green

22