11.4Control Wires

The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8.

 

 

 

 

 

Table 11.8 EXTERNAL CONNECTIONS

No.

 

I/O

 

 

Signal Name

 

Operation

1

 

Output

 

 

Low Battery

 

Closed at Low Battery

2

 

Output

 

 

Backup Operation

 

Closed during Backup Operation

3

 

Output

 

 

Fault

 

Closed if Faults present

4

 

Output

 

 

Inverter Supply

 

Closed during Normal Operation

5

 

Output

 

 

Warning

 

Closed if Warnings present

6

 

Input

}

 

P24

 

 

7

 

Input

 

Remote Run

 

Close to run UPS

 

 

 

8

 

Input

}

 

P24

 

 

9

 

Input

 

Remote Stop

 

Close to stop UPS

 

 

 

10

 

Output

 

 

Bypass Supply

 

Close during Bypass Operation

11

 

Output

 

 

Output Signal Ground

 

(Ground for pin #1 – 5 & #10)

12

 

Input

}

 

P24

 

Battery’s

13

 

Input

 

Battery Overheat

 

Overheat B-contact

 

 

 

14

 

Output

}

 

 

 

Bypass Breaker

15

 

Output

 

52C Trip Signal

 

Shunt Trip Signal by EPO

 

 

 

16

 

Output

}

 

 

 

Battery Breaker shunt trip

17

 

Output

 

72B Trip Signal

 

by EPO or Battery shutdown

 

 

 

18

 

Output

}

 

 

 

Battery breaker’s

19

 

Output

 

72B Aux. Contact

 

Auxiliary A-contact

 

 

 

20

 

 

 

 

 

 

 

21

 

Output

}

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

22

 

Output

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

 

 

 

Note: All control wiring should be #18 AWG (0.823 mm2) or larger.

38

G8000 Series Installation and Operation Manual

Page 46
Image 46
Toshiba G8000 operation manual Control Wires, Signal Name Operation