Page 66
Image 66

Function list (Extended function parameters)

 

 

 

 

 

 

At-a-glance Guide to Func-

 

 

 

 

 

 

 

tions

 

 

 

 

 

 

 

": Usable function

Function

Parameter

 

 

 

Cus-

×: Unusable function

 

 

 

 

 

* : Functions that can be used

 

 

Name

Outline

Factory

tomer

 

 

for param eter-set position con-

 

 

Setting

Set-

 

 

 

 

 

trol

 

 

 

 

 

 

ting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vector Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

Torque

Position

 

 

 

 

 

 

control

control

control

 

 

232

Multi-speed setting

By setting any value other than "9999", set speeds 8 to 15.

 

 

9999

"

"

× *

 

 

 

(speed 8)

 

 

 

 

 

 

 

 

 

 

This function is designed to change the running speed in stages by changing the ON/

 

 

 

 

 

 

 

Multi-speed setting

 

 

 

× *

 

 

233

OFF combination of the contact signals (RH, RM, RL, REX signals).

9999

"

"

 

 

(speed 9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

234

Multi-speed setting

 

 

 

 

 

 

 

 

 

9999

"

"

× *

operation

 

Speed 9

 

RH

 

RM

RL

REX

 

235

(speed 11)

 

 

OFF

 

OFF

ON

ON

 

9999

"

"

× *

 

 

 

(speed 10)

 

 

 

 

 

 

 

 

 

 

 

 

 

speed-Multi

 

Multi-speed setting

 

Speed 8

 

OFF

 

OFF

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 10

 

OFF

 

ON

OFF

ON

 

 

 

 

 

 

 

236

Multi-speed setting

 

 

 

 

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 11

 

OFF

 

ON

ON

ON

 

 

 

(speed 12)

 

 

 

 

 

 

 

 

 

Speed 12

 

ON

 

OFF

OFF

ON

 

 

 

 

 

 

 

237

Multi-speed setting

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

(speed 13)

 

Speed 13

 

ON

 

OFF

ON

ON

 

 

 

 

 

 

Speed 14

 

ON

 

ON

OFF

ON

 

 

 

 

 

 

 

238

Multi-speed setting

 

 

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 15

 

ON

 

ON

ON

ON

 

 

 

 

(speed 14)

 

 

 

 

 

 

 

 

 

 

239

Multi-speed setting

0 to 3600r/min, 9999

 

 

 

 

 

 

9999

"

"

× *

 

 

 

(speed 15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can select to exercise Soft-PWM control and

long wiring mode. When Soft-PWM

 

 

 

 

 

 

 

 

control is made valid, you can change the metallic tone of motor sound into an

 

 

 

 

 

 

 

 

unoffending complex tone. Surge voltage is surpressed in the long wiring mode

 

 

 

 

 

 

 

 

regardless of the wiring length between the inverter and motor. (When operating a

 

 

 

 

functions

240

Soft-PWM setting

400V motor with wiring length of 40m or more, select long wiring mode.)

10

"

"

"

10: Soft-PWM control invalid, long wiring mode valid (carrier frequency is 2.25Hz *)

 

 

 

 

0: Soft-PWM control invalid, long wiring mode invalid

 

 

 

 

 

 

 

 

 

 

1: Soft-PWM control valid (when Pr. 72 = "1 or 2"), long wiring mode invalid

 

 

 

 

Sub

 

 

11: Soft-PWM control valid, long wiring mode valid (carrier frequency is 2.25Hz *)

 

 

 

 

 

 

 

*The Pr.72 "PWM frequency selection" setting is made invalid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling fan operation

You can control the operation of the cooling fan built in the inverter.

 

 

 

 

 

 

244

0: The fan is always operated at power-on of the inverter.

 

 

0

"

"

"

 

 

 

selection

1: The fan is always on while the inverter is running. During a stop, the inverter status is

 

 

 

 

 

 

 

 

monitored and the fan switches on-off according to the temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selectionStop

function

 

 

Set to allow the motor to be coasted to a stop by turning off the start command during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

Stop selection

V/F or speed control.

 

 

 

 

 

 

9999

"

"

×

 

 

0 to 100s: Coasting to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9999: Deceleration to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selectionOperation

function

 

Output phase failure

You can disable the output phase failure function that stops the inverter output if one of

 

 

 

 

 

 

 

 

 

 

 

 

 

251

the inverter output side (load side) three phases (U, V, W) opens.

1

"

"

"

 

 

 

protection selection

0: Without output phase failure protection

 

 

 

 

 

 

 

 

 

 

 

 

1: With output phase failure protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional

functions

253

Override gain

 

 

 

 

 

 

 

 

 

150%

"

"

×

 

 

252

Override bias

When you selected the override in Pr. 73, you can adjust the override bias (0 to 200%)

50%

"

"

×

 

 

 

 

and override gain (0 to 200%).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

261

Power failure stop

You can select the stopping method at a power failure.

 

 

 

"

"

×

 

 

0: Coasting to stop, inverter output shutoff

 

 

 

0

 

 

 

selection

1: Inverter is decelerated to a stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

263

Subtraction starting

0 to 3600r/min, 9999

 

 

 

 

 

 

1500r/m in

"

"

×

 

 

262

Subtracted speed at

0 to 600r/min

 

 

 

 

 

 

90r/min

"

"

×

 

 

 

deceleration start

 

 

 

 

 

 

 

 

 

 

 

 

 

stop

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

failure

264

Power-failure

0 to 3600/0 to 360s

 

 

 

 

 

 

5s

"

"

×

 

deceleration time 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

265

Power-failure

0 to 3600/0 to 360s, 9999

 

 

 

 

 

 

9999

"

"

×

 

deceleration time 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power-failure

 

 

 

 

 

 

 

 

 

 

 

 

×

 

 

266

deceleration time

0 to 3600r/min

 

 

 

 

 

 

1500r/m in

"

"

 

 

 

switchover speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

278

Brake opening speed

 

 

 

 

 

 

 

 

 

20r/min

"

×

×

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

279

Brake opening

 

 

 

 

 

 

 

 

 

130%

"

×

×

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

280

Brake opening

Set when outputting the operation timing signal of the mechanical brake in vertical lift

0.3s

"

×

×

 

 

current detection time

sequence

applications. (When speed control (invalid for V/F control) is selected)

282

Brake operation speed

0 to 5s (Pr. 281)

 

 

 

 

 

 

25r/min

"

×

×

 

 

281

Brake operation time

0 to 900r/min (Pr. 278)

 

 

 

 

 

 

0.3s

"

×

×

 

 

at start

0 to 200% (Pr. 279)

 

 

 

 

 

 

Brake

 

 

0 to 2s (Pr. 280)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 900r/min (Pr. 282)

 

 

 

 

 

 

 

 

 

 

 

 

283

Brake operation time

 

 

 

 

 

 

0.3s

"

×

×

 

 

0 to 5s (Pr. 283)

 

 

 

 

 

 

 

 

 

at stop

0, 1 (Pr. 284)

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration

0 to 900r/min, 9999 (Pr. 285)

 

 

 

 

 

 

 

 

×

×

 

 

284

detection function

 

 

 

 

 

 

 

 

 

0

"

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

285

Overspeed detection

 

 

 

 

 

 

 

 

 

9999

"

×

×

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

PARAMETERS

Parameter

5

62

Page 66