Function list (Extended function parameters)

 

 

 

 

 

 

 

At-a-glance Guide to Func-

 

 

 

 

 

 

 

 

tions

 

 

 

 

 

 

 

 

": Usable function

Function

Parameter

 

 

 

Cus-

×: Unusable function

 

 

 

 

 

 

* : Functions that can be used

 

 

 

Name

Outline

Factory

tomer

 

 

 

for param eter-set position con-

 

 

 

Setting

Set-

 

 

 

 

 

 

trol

 

 

 

 

 

 

 

ting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vector Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

Torque

Position

 

 

 

 

 

 

 

control

control

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can select the monitor output DA1 data.

 

 

 

 

 

 

 

 

 

1: Speed

 

 

 

 

 

 

 

 

 

2: Output current

 

 

 

 

 

 

 

 

 

3: Output voltage

 

 

 

 

 

 

 

 

 

5: Preset speed

 

 

 

 

 

 

 

 

 

6: Output frequency

 

 

 

 

 

 

 

 

 

7: Motor torque

 

 

 

 

 

 

 

 

 

8: Converter output voltage

 

 

 

 

 

 

 

54

DA1 terminal function

9: Regenerative brake duty

1

 

"

"

"

functions

selection

10: Electronic thermal relay load factor

 

 

11: Output current peak value

 

 

 

 

 

 

 

18: Motor exciting current

 

 

 

 

 

 

 

 

 

12: Converter output voltage peak value

 

 

 

 

 

Display

 

 

17: Load meter

 

 

 

 

 

 

 

21: Reference output

 

 

 

 

 

 

 

 

 

32: Torque command

 

 

 

 

 

 

 

 

 

33: Torque current command

 

 

 

 

 

 

 

 

 

34: Motor output

 

 

 

 

 

 

 

 

 

36: Torque monitor (driving/regenerative polarity switching)

 

 

 

 

 

 

 

55

Speed monitoring

You can set the reference value of speed monitoring.

1500r/m in

 

"

"

"

 

 

 

reference

0 to 3600r/min

 

 

 

 

 

 

 

 

Current monitoring

 

Rated

 

 

 

 

 

 

56

You can set the reference value of current monitoring.

inverter

 

"

"

"

 

 

 

reference

0 to 500A

output

 

 

 

 

 

 

 

 

 

current

 

 

 

 

restart

57

Restart coasting time

When power is restored after an instantaneous power failure, you can start the inverter

9999

 

"

"

×

 

 

without stopping the motor (in a coasting status). When this time (Pr. 57) elapses after

 

 

 

 

 

 

 

 

 

power was restored, the inverter begins to restart.

 

 

 

 

 

Automatic

 

 

When you set "9999", the inverter will not restart. Generally, you may set "0", but you

 

 

 

 

 

58

Restart cushion time

can adjust the time (0, 0.1 to 5s, 9999) according to the load magnitude.

1.0s

 

×

×

×

 

 

When the restart coasting time (Pr. 57) elapses, the output voltage is risen gradually.

 

 

 

 

 

Set this cushion time (Pr. 58) (0 to 60s).

 

 

 

 

 

 

 

 

 

Normally, you can perform operation with the factory settings, but you can adjust them

 

 

 

 

 

 

 

 

 

according to the load magnitude. Pr. 58 is valid only during V/F control.

 

 

 

 

 

function

 

 

0: None

 

 

 

 

 

 

 

 

 

You can make remote setting of the speed when the operation panel is located away

 

 

 

 

 

 

 

 

 

from the control box.

 

 

 

 

 

dditional

59

Remote setting

1: With remote setting function, with frequency setting storage function

0

 

"

"

×

 

function selection

2: With remote setting function, without frequency setting storage function

 

 

 

 

 

 

 

 

 

3: With remote setting function, without frequency setting storage function

 

 

 

 

 

A

 

 

(Turning STF/STR off clears remote setting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set when using the brake sequence control.

 

 

 

 

 

 

 

 

Intelligent mode

0: Normal operation mode

 

 

 

 

 

 

 

60

7: Brake sequence mode

0

 

"

×

×

 

 

 

selection

(With mechanical brake opening completion signal input)

 

 

 

 

 

 

 

 

 

8: Brake sequence mode

 

 

 

 

 

 

 

 

 

(Without mechanical brake opening completion signal input)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can select alarms for a retry to be made when the protective function is activated.

 

 

 

 

 

functions

 

 

0:E.OC1 to 3, E.OV1 to 3, E.THM, E.THT, E.IPF, E.UVT, E.BF, E.GF, E.OHT, E.OLT,

 

 

 

 

 

 

 

E.OPT, E.OP1 to 3, E.PE, E.OS, E.OSD, E.OD, E.MB1 to 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

Retry selection

1:E.OC1 to 3

 

 

"

"

×

 

 

2:E.OV1 to 3

0

 

selection

 

 

3:E.OC1 to 3, E.OV1 to 3

 

 

 

 

 

 

 

4:E.OC1 to 3, E.OV1 to 3, E.IPF, E.UVT, E.BF, E.GF, E.OLT, E.OPT, E.OP1 to 3, E.PE,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E.OS, E.OSD, E.OD, E. MB1 to 7

 

 

 

 

 

 

 

 

 

5:E.OC1, E.OC3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

101 to 110: With alarm output during retry operation

 

 

 

 

 

 

 

 

Number of retries at

You can set the number of retries to be made when the protective function is activated.

 

 

 

 

 

 

 

67

0: Retry not made.

0

 

"

"

×

 

 

 

alarm occurrence

1 to 10: Without alarm output during retry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

Retry waiting time

You can set the waiting time from activation of the protective function to a retry.

1s

 

"

"

×

 

 

0 to 10s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69

Retry count display

You can display the cumulative number of successful restarts made by retries when the

 

 

"

"

×

 

 

protective function was activated.

0

 

 

 

 

erasure

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

Special regenerative

Set to increase the regenerative brake duty when the FR-ABR option is used.

0%

 

"

"

"

 

 

 

brake duty

0 to 15%(1.5K or less), 0 to 30%(2.2K or more)

 

 

 

 

 

PARAMETERS

Parameter

5

56

Page 60
Image 60