Errors (Alarms)

Operation Panel

E. 6

 

FR-PU04V

Fault 6

 

 

 

Indication

 

 

 

E. 7

 

Fault 7

 

 

 

 

 

 

 

 

 

 

Name

CPU error

 

 

 

 

If the arithmetic operation of the peripheral circuit of the built-in CPU does not end within the

Description

predetermined period or if an error exists in the receive data of the built-in CPU, the inverter self-

 

determines it as an alarm and stops the output.

 

 

 

 

 

Check point

 

 

Corrective action

Please contact your sales representative.

 

 

 

 

 

 

Operation Panel

E.P24

 

FR-PU04V

E.P24

Indication

 

 

 

 

 

 

 

 

 

 

Name

24VDC power

output short circuit

 

 

 

When the 24VDC power output from the PC terminal is shorted, this function shuts off the power

 

output.

 

 

Description

At this time, all external contact inputs switch off. The inverter cannot be reset by entering the RES

 

signal. To reset it, use the operation panel or switch power off, then on again.

 

When the 24VDC power for encoder is shorted, this function shuts off the power output.

 

 

 

 

• Check for a short circuit in the PC terminal output.

 

Check point

• Check for wrong wiring.

 

 

 

• Check for a loose connector. Check that the cables are short-circuited.

 

 

 

 

Corrective action

• Remedy the short circuit portion.

 

 

• Connect the cables securely. Change the cables.

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.P12

 

FR-PU04V

E.P12

Indication

 

 

 

 

 

 

 

 

 

 

Name

12VDC power

output short circuit

 

 

Description

When the 12VDC power for encoder is shorted, this function shuts off the power output.

Check for wrong wiring.

Check point

Check for a loose connector. Check for an open cable.

Corrective action Connect the cables securely. Change the cables.

Operation Panel

E.CTE

 

 

 

FR-PU04V

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Operation panel power supply short circuit

 

 

When the operation panel power supply (P5S of the PU connector) is shorted, this function shuts

 

off the power output. At this time, the operation panel (parameter unit) cannot be used and RS-485

Description

communication from the PU connector cannot be made. To reset, enter the RES signal or switch

 

power off, then on again.

 

 

 

 

 

 

When the 5VDC power for encoder is shorted, this function shuts off the power output.

 

 

 

• Check for a short circuit in the PU connector cable. Check for a loose connector.

Check point

• Check that cables are short-circuited.

 

 

 

 

• Check for wrong wiring.

 

 

 

 

 

 

 

 

 

 

 

 

Corrective action

• Check the PU and cable.

 

 

 

 

 

• Connect the cable securely. Change the cable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.MB1 to 7

 

to

 

FR-PU04V

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Brake sequence

error

 

 

 

 

 

 

• The inverter output is stopped when a sequence error occurs during use of the brake sequence

Description

function (Pr. 278 to Pr. 285).

 

 

 

• If (detection frequency) - (output frequency) > Pr. 285 under vector control, E.MB1 occurs and the

 

 

inverter output is stopped.

 

 

 

 

 

 

 

 

 

 

Check point

Find the cause of alarm occurrence.

 

 

 

Corrective action

Check the set parameters and perform wiring properly.

 

75

Page 79
Image 79
Mitsubishi Electronics FR-V500 Indication Fault Name, Operation Panel P24, Operation Panel P12, Operation Panel MB1 to