Errors (Alarms)

Operation Panel

RB

 

FR-PU04V

RB

Indication

 

 

 

 

 

 

 

 

 

 

Name

Regenerative

brake prealarm

 

 

 

Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "special regenerative

Description

brake duty" value. If the regenerative brake duty reaches 100%, a regenerative overvoltage

 

(E. OV_) occurs.

 

 

 

 

 

 

• Check that the brake resistor duty is not high.

 

Check point

• Check that the Pr. 30 "regenerative function selection" and Pr. 70 "special regenerative brake

 

duty" values are correct.

 

 

 

 

 

 

 

• Increase the deceleration time.

 

 

Corrective action

• Check the Pr. 30 "regenerative function selection" and Pr. 70 "special regenerative brake duty"

 

values.

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

TH

 

FR-PU04V

TH

Indication

 

 

 

 

 

 

 

 

 

 

Name

Electronic thermal relay prealarm

 

 

Description

Appears if the integrating value of the electronic thermal relay reaches or exceeds 85% of the

preset level. If it reaches 100% of the preset level, a motor overload shutoff (E. THM) occurs.

 

 

 

 

Check point

Check for large load or sudden acceleration.

 

Corrective action

Reduce the load weight or the number of operation times.

 

 

 

 

 

Operation Panel

MT

 

FR-PU04V

MT

Indication

 

 

 

 

 

 

 

 

 

 

Name

Maintenance

signal output

 

 

Description

Indicates that the cumulative energization time of the inverter has reached a given time.

Check point

Check that Pr. 890 "maintenance output setting time" has been set. (A short time has been set.)

Corrective action

After checking the energization time, write "0" to Pr. 892 "maintenance output signal clear".

 

 

 

 

 

Operation Panel

SL

 

FR-PU04V

SL

Indication

 

 

 

 

 

 

 

 

 

 

Name

Speed limit

indication (speed restriction)

 

Description

Output if the speed restriction level is exceeded during torque control.

Check point

• Check that the torque command is not larger than required.

• Check that the speed restriction level is not low.

 

 

 

 

 

Corrective action

Decrease the torque restriction. Increase the speed restriction level.

 

 

 

 

 

Operation Panel

Err.

 

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm appears if:

 

 

 

• The RES signal is on;

 

 

 

• You attempted to make parameter setting in the external operation mode;

 

• You attempted to change the operation mode during operation;

Description

• You attempted to set any parameter value outside its setting range;

 

• The PU and inverter cannot make normal communication;

 

• You attempted to make parameter setting during operation (when signal STF or STR is on); or

 

• You attempted to make parameter setting when Pr. 77 "parameter write disable selection" has

 

been set to disable parameter write.

 

 

 

 

 

 

Corrective action

Perform run and operation securely.

 

 

ERRORS AND PROTECTIVE FUNCTIONS

6

78

Page 82
Image 82
Mitsubishi Electronics FR-V500 instruction manual Operation Panel Err Indication