Basic configuration and connection of peripheral devices

1.1 Basic configuration and connection of peripheral devices

1.1.1Basic configuration

Power supply

Use within the permissible power supply specifications of the inverter. (Refer to page 99.)

(NFB)

No-fuse breaker (NFB) or earth leakage circuit braker (ELB)

or

The breaker must be selected carefully since an in-rush current flows in the inverter at

(ELB)

power-on. (Refer to page 3.)

 

(MC)

Magnetic contactor

Install the magnetic contactor to ensure safety. (For details, refer to the Instruction Manual

 

(detailed).)

 

Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the

 

inverter life to be shorten.(Refer to page 3.)

AC reactor (FR-BAL)

Line noise filter

Radio noise filter

Inverter

FR-V500

RST

Power factor

 

 

P

improvement

 

 

 

 

 

 

reactor

 

 

P1

Brake resister

 

 

P

 

 

 

 

 

 

(FR-ABR)

 

 

PR

 

 

 

 

Brake unit

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line noise filter

PLG cable

Earth(Ground)

Noise filter

Install a noise filter to reduce the magnetic noise generated from the inverter. (Refer to the instruction manual of each option for details.)

Line noise filter (FR-BSF01) (FR-BLF)

Effective in the range from about 1MHz to 10MHz. When more wires are passed through, a more effective result can be obtained.(Note that the number of wires run through is limited when fitting to the output side.)

Radio noise filter (FR-BIF)

Effective in reducing the noises in the AM radio frequency band. Dedicated filter for the

input side.

Power factor improvement reactor

Reactors must be used when the power factor is to be improved or when the inverter is installed near a large power supply system (1000kVA or more and wiring distance is within 10m). The inverter may be damaged if you do not use reactors.

Make selection carefully. (Refer to page 3.)

(Refer to the instruction manual of each option for details.)

• DC reactor (FR-BEL), AC reactor (FR-BAL)

(Caution) Remove the jumpers across terminals P-P1 to connect to the PC reactor.

Inverter

The life of the inverter is influenced by am bient tem perature. The am bient tem perature should be as low as possible within the perm issible range. This m ust be noted especially when the inverter is installed in an enclosure. (Refer to page 6.) W rong wiring m ight lead to dam age of the inverter. The control signal lines m ust be kept fully away from the m ain circuit to protect them from noise. (Refer to page 7.)

Brake resistor

(Refer to the instruction manual of each option for details)

(Caution) • Remove the jumpers across terminals PR-PX to connect to the inverter.

Set "1" in Pr. 30 "regenerative function selection".

Set "10%" in Pr. 70 "special regenerative brake duty".

Brake unit

(Refer to the instruction manual of each option for details)

(Caution) Remove the jumpers across terminals PR-PX to connect to the inverter.

Power regeneration common converter (FR-CV)

(Refer to the instruction manual of each option for details.) (Caution) • Remove the jumpers across terminals R-R1 and S-S1.

For a terminal to be connected to the RDYB signal of the FR-CV, set "10" (X10 signal) in any of Pr. 180 to Pr. 183 and Pr. 187(input terminal function selection).

Set "2" in Pr. 30 "regenerative function selection".

Select the converter one rank higher in capacity than the inverter.

Selection example: FR-V520-7.5KFR-CV-11K, FR-V520-15KFR-CV-18.5K (When connecting two inverters to one FR-CV, the capacity is 11K + 18.5K =

29.5K. Therefore, select FR-CV-30K.)

Motor

!Dedicated motor (Refer to page 99.)

This is a highly environmentally-resistant motor based on a totally-enclosed squirrel- cage induction motor designed for the vector inverter. Select the motor that matches the inverter capacity.

PLG

For the PLG dedicated motor, refer to page 12.

Devices connected to the output

Do not install a power factor correction capacitor, surge suppressor or radio noise filter (FR- BIF option) in the output side of the inverter.

Earth (Ground)

To prevent an electric shock, always earth (ground) the motor and inverter. For reduction of induction noise from the power line of the inverter, it is recommended to wire the earth (ground) cable by returning it to the earth (ground) terminal of the inverter.

( For details of noise reduction techniques, refer to the Instruction Manual (detailed).