Torque control operation

(1) I/O signals

The following table indicates the operations of the signals.

Signal

 

Terminal Name

Remarks

 

 

 

 

 

 

External operation

 

STF, STR signal

Start and stop are the same as under speed

Start signal

PU operation

 

Forward or reverse rotation from

control. A stop is made when the STF and

 

 

PU04V or DU04-1

STR signals are both on.

 

 

 

 

 

 

 

Torque command

As set in the torque command right selection parameter.

Input torque command.

 

 

 

 

 

Speed restriction

As set in the speed restriction selection parameter.

Display SL and output OL signal during speed

restriction.

 

 

 

 

 

 

 

 

 

(2) Operation example (Pr. 804=0)

Torque control is enabled if the actual speed is less than the speed restriction value.

When the actual speed reaches or exceeds the speed restriction value, speed restriction operation starts, torque control is stopped, and speed control (proportional control) starts.

The following shows the operations in response to the analog input command from the No. 3 terminal.

Pr. 7

Speed restriction value

Pr. 8

 

STF (Forward rotation command)

RH (Speed restriction)

Speed restriction

Torque control operation

Speed restriction

Torque

Speed restriction

 

operation

 

operation

control

operation

 

 

(Speed control)

operation

 

1)When STF is turned on, the speed restriction value is increased according to the time set in Pr. 7.

2)Torque control operation is performed when the actual speed is less than the speed restriction value.

3)When the STF start signal is turned off, the speed restriction value is decreased according to the time set in Pr. 8.

4)For torque control, the actual speed becomes constant when the torque command and load torque are bal- anced.

5)The motor torque developing direction is determined by the combination of the torque command input polarity and start signal as indicated in the following table.

Torque Command Polarity

Torque Developing Direction (Mode)

 

 

STF signal ON

STR signal ON

 

 

 

 

Positive torque command

Forward rotation direction (forward rotation

Reverse rotation direction (forward rotation

driving/reverse rotation regeneration)

regeneration/reverse rotation driving)

 

 

 

 

Negative torque command

Reverse rotation direction (forward rotation

Forward rotation direction (forward rotation

regeneration/reverse rotation driving)

driving/reverse rotation regeneration)

 

 

 

 

REMARKS

When speed restriction operation starts, speed control is exercised to enable internal torque restriction (Pr. 22 "torque restric- tion level) (factory setting). Speed control may not be returned to torque control in this case. Torque restriction be set to exter- nal torque restriction (terminals No. 3, No. 1 and No. 6 (option FR-V5AX).

(Refer to Pr. 803 "constant output region torque characteristic selection" (page 33).)

37

Page 41
Image 41
Mitsubishi Electronics FR-V500 O signals, Operation example Pr =0, Following table indicates the operations of the signals