Precautions for maintenance and inspection

6.5.5Pressure test

Do not conduct a pressure test. Deterioration may occur.

6.5.6Daily and periodic inspection

 

 

 

Interval

 

 

 

Customer’s check

 

 

 

 

 

 

 

 

 

Area of

Inspection

Description

 

Periodic*

Method

Criterion

Instrument

 

 

 

Inspection

Item

Daily

1 year

2 years

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

 

 

 

 

 

temperature: -10°C

 

 

 

Surrounding

Check ambient

 

 

 

Measure 5cm away from

to +50°C , non-

Thermometer,

 

 

temperature, humidity,

"

 

 

the inverter.

freezing.

hygrometer,

 

 

environment

 

 

 

 

dust, dirt, etc.

 

 

 

(Refer to page 6.)

Ambient humidity:

recorder

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90% or less, non-

 

 

General

 

 

 

 

 

 

condensing.

 

 

 

Overall unit

Check for unusual

"

 

 

Visual and auditory

No fault.

 

 

 

vibration and noise.

 

 

checks.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check that the main

 

 

 

Measure voltages

Within permissible

 

 

 

Power supply

 

 

 

across the inverter

AC (DC) voltage

Tester, digital

 

 

circuit voltages are

"

 

 

 

 

voltage

normal.

 

 

 

terminal block R, S and

fluctuation (refer to

multimeter

 

 

 

 

 

 

T phases.

page 99)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check with megger

 

 

 

(1) Disconnect all cables

 

 

 

 

 

(across main circuit

 

 

 

from the inverter and

 

 

 

 

 

terminals and earth

 

 

 

measure across

 

 

 

 

General

(ground) terminal).

 

"

"

terminals R, S, T, U,

(1) 5Mor more.

500VDC

 

 

(2) Check for loose

 

V, W and earth

(2), (3) No fault.

class megger

 

 

 

screws and bolts.

 

 

 

terminal with

 

 

 

 

 

 

 

 

 

 

 

(3) Check for overheat

 

"

 

megger.

 

 

 

 

 

traces on the parts.

 

 

 

(2) Retighten.

 

 

 

 

 

(4) Clean.

 

"

 

(3) Visual check.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check conductors

 

"

 

 

 

 

 

 

Conductors,

for distortion.

 

 

 

 

 

 

 

 

(2) Check cable

 

"

 

(1), (2) Visual check.

(1), (2) No fault.

 

 

 

cables

 

 

 

 

Main circuit

sheaths for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

breakage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal block

Check for damage.

 

"

 

Visual check

No fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check for chatter

 

"

 

 

 

 

 

 

Relay

during operation.

 

 

 

(1) Auditory check.

(1), (2) No fault.

 

 

 

(2) Check for rough

 

"

 

(2) Visual check.

 

 

 

 

 

 

 

 

 

 

 

surface on contacts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Visual check.

 

 

 

 

 

(1) Check for crack in

 

"

 

Cement resistance,

 

 

 

 

Resistor

resistor insulation.

 

 

 

wire-wound resistor.

(1) No fault.

 

 

 

(2) Check for open

 

"

 

(2) Disconnect one end

(2) Indication

 

 

 

 

 

 

 

 

 

 

cable.

 

 

 

and measure with

 

 

 

 

 

 

 

 

 

tester.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check balance of

 

"

 

(1) Measure voltages

 

 

 

 

 

output voltages

 

 

 

 

 

 

 

 

 

 

 

across the inverter

(1) Phase-to-phase

 

 

 

 

across phases with

 

 

 

 

 

 

 

 

 

 

output terminals U-

voltage balance

 

 

Control cir-

 

the inverter

 

 

 

Digital

 

cuit

Operation

operated alone.

 

 

 

V-W.

within 4V (8V) for

multimeter,

 

Protective

check

(2) Perform sequence

 

"

 

(2) Simulatively short or

200V (400V).

rectifier type

 

 

 

open the protective

(2) Fault must occur

 

circuit

 

protective operation

 

 

 

voltmeter

 

 

 

test to ensure no

 

 

 

circuit output

because of

 

 

 

 

 

 

 

terminals of the

sequence.

 

 

 

 

fault in protective

 

 

 

 

 

 

 

 

 

 

inverter.

 

 

 

 

 

and display circuits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check for unusual

"

 

 

(1) Turn by hand with

 

 

 

Cooling

 

vibration and noise.

 

 

 

No unusual vibration

 

 

Cooling fan

 

 

"

power off.

 

 

system

(2) Check for loose

"

"

and noise.

 

 

 

 

connection.

 

 

 

(2) Visual check.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERRORS AND PROTECTIVE FUNCTIONS

6

94

Page 98
Image 98
Mitsubishi Electronics FR-V500 Precautions for maintenance and inspection Pressure test, Daily and periodic inspection