Errors (Alarms)

Operation Panel

E. 1 to

 

to

FR-PU04V

 

Fault 1 to Fault 3

Indication

E. 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Option alarm

 

 

 

 

 

Description

Stops the inverter output if a contact fault or the like of the connector between the inverter and

communication option occurs.

 

 

 

 

 

Check point

Check that the communication option is plugged into the connector securely.

(1 to 3 indicate the option slot numbers.)

 

 

 

 

 

 

Corrective action

• Connect the plug-in option securely.

 

• Please contact your sales representative.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.PE

 

 

FR-PU04V

 

Corrupt Memry

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Parameter storage device alarm

 

Description

Appears when an error occurred in the stored parameters. (E2PROM fault)

Check point

Check for too many number of parameter write times.

 

 

• Please contact your sales representative.

 

Corrective action

• When performing parameter write frequently for communication purposes, set "1" in Pr. 342 to

 

enable RAM write. Note that powering off returns the inverter to the status before RAM write.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.PUE

 

 

FR-PU04V

 

PU Leave Out

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

PU disconnection

 

 

 

 

 

This function stops the inverter output if communication between the inverter and PU is suspended,

 

e.g. the operation panel or parameter unit is disconnected, when "2", "3", "16" or "17" was set in Pr.

 

75 "reset selection/disconnected PU detection/PU stop selection". This function stops the inverter

Description

output if the number of successive communication errors is greater than the permissible number of

 

retries when the Pr. 121 value is other than "9999" for RS-485 communication from the PU

 

connector. This function also stops the inverter output if communication is broken for the period of

 

time set in Pr. 122.

 

 

 

 

 

 

Check point

• Check for loose fitting of the FR-DU04-1or FR-PU04V.

• Check the Pr. 75 setting.

 

 

 

 

 

 

 

 

 

 

 

 

Corrective action

Fit the FR-DU04-1or FR-PU04V securely.

 

 

 

 

 

 

 

 

Operation Panel

E.RET

 

 

FR-PU04V

 

Retry No Over

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Retry count

excess

 

 

 

 

Description

If operation cannot be resumed properly within the number of retries set, this function stops the

inverter output.

 

 

 

 

 

 

 

 

 

 

 

 

Check point

Find the cause of alarm occurrence.

 

Corrective action

Eliminate the cause of the error preceding this error indication.

 

 

 

 

 

 

 

Operation Panel

E.LF

 

 

FR-PU04V

 

ELF

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Output phase

failure protection

 

 

 

Description

This function stops the inverter output if one of the three phases (U, V, W) on the inverter's output

side (load side) opens.

 

 

 

 

 

 

 

 

 

 

 

 

Check point

• Check the wiring (Check the motor for a fault.)

 

• Check that the capacity of the motor used is not smaller than that of the inverter.

 

 

 

 

 

 

 

Corrective action

• Wire the cables properly.

 

 

 

 

• Check the Pr. 251 "output phase failure protection selection" setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.CPU

 

 

FR-PU04V

 

CPU Fault

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

CPU error

 

 

 

 

 

Description

Stops the inverter output if the communication error of the built-in CPU occurs.

Check point

 

 

 

 

Corrective action

Please contact your sales representative.

 

ERRORS AND PROTECTIVE FUNCTIONS

6

74