Troubleshooting

6.4.8Torque control is not exercised normally

(1) Torque control

Torque control is not exercised normally.

Is torque control selected in control mode selection (Pr. 800)?

Y

Is the phase sequence

of the motor wiring correct?

Y

Have you set the motor type?

N

Select torque control in control mode selection (Pr. 800).

N

Check the wiring and perform correct wiring.

N

Y

Is the vector inverter motor (SF-V5R,SF-VR), standard motor with PLG (SF-JR) or constant-torque motor with PLG (SF-HRCA) used?

Set the motor in motor setting (Pr. 71).

N

Y

Is the wiring length short?

Y

Is the phase sequence of the PLG correct?

Y

Have you set the number of PLG pulses (Pr. 851) and is it correct?

Y

Does the voltage of the torque command signal (across 3-5) change?

Y

Does the torque command value match the inverter- recognized value?

Y

Have you set the speed restriction level and is that value correct?

Y

N

Perform offline auto tuning (Pr. 71, Pr. 80, Pr. 81, Pr. 83, Pr. 84, Pr. 96) or enter the motor constants (Pr. 90 to Pr. 94).

N

Perform correct wiring.

N

Set the number of PLG pulses

(Pr. 851).

N

Speed setting potentiometer fault Open cable between the setting potentiometer and terminal

N

Calibrate the torque command bias/gain No. 3 terminal

(Pr. 904, Pr. 905).

N

 

N

Is an external

command used?

 

Y

Is an analog input used?

Y

Calibrate the speed setting bias/gain

No. 2 terminal (Pr. 902, Pr. 903).

1 Page 92

Set speed restriction in the parameters (Pr. 805 to Pr. 807).

N

 

Is the corresponding

 

N

 

multi-speed signal

 

 

 

 

 

 

 

(RH, RM, RL, REX) on?

 

 

 

Y

Turn on the multi-speed

 

signal (RH, RM, RL, REX).

Check the multi-speed settings

 

(Pr. 4 to 6, 24 to 27, 232 to 239).

 