Mitsubishi Electronics FR-V500 Inst. Pwr. Loss, Under Voltage, Sink O/Temp, Br. Cct. Fault

Models: FR-V500

1 112
Download 112 pages 3.61 Kb
Page 76
Image 76

Errors (Alarms)

Operation Panel

E.IPF

 

FR-PU04V

Inst. Pwr. Loss

Indication

 

 

 

 

 

 

 

 

 

 

Name

Instantaneous

power failure protection

(*4)

 

 

If a power failure occurs for longer than 15ms (this also applies to inverter input shut-off), the

 

instantaneous power failure protective function is activated to stop the inverter output in order to

 

prevent the control circuit from malfunctioning. At this time, the alarm warning output contacts open

Description

(across terminals B-C) and close (across terminals A-C). If a power failure persists for longer than

 

100ms, the alarm warning output is not provided, and the inverter restarts if the start signal is on

 

upon power restoration. (The inverter continues operating if an instantaneous power failure is

 

within 15ms.)

 

 

 

 

Check point

Find the cause of instantaneous power failure occurrence.

 

• Remedy the instantaneous power failure.

Corrective action

• Prepare a backup power supply for instantaneous power failure.

• Set the function of automatic restart after instantaneous power failure (Pr. 57).

 

 

(Refer to page 56.)

 

 

 

 

 

 

 

*4: When an instantaneous power failure occurs, the alarm display and alarm output are not provided, but the inverter performs protective operation to prevent a fault from occurring in itself. In some operating status (load magnitude, acceleration/deceleration time setting, etc.), overcurrent or other protection may be activated upon power restoration.

Operation Panel

E.UVT

 

FR-PU04V

Under Voltage

Indication

 

 

 

 

 

 

 

 

 

 

Name

Undervoltage

protection

 

 

 

If the power supply voltage of the inverter reduces, the control circuit will not perform normal

 

functions. In addition, the motor torque wiil be insufficient and/or heat generation will increase. To

Description

prevent this, if the power supply voltage reduces below about 150V (300V for the 400V class), this

 

function stops the inverter output.

 

 

 

When a jumper is not connected across P-P1, the undervoltage protective function is activated.

 

 

 

Check point

• Check for start of large-capacity motor.

 

• Check that a jumper or DC reactor is connected across terminals P-P1.

 

 

 

Corrective action

Check the power supply system equipment such as power supply.

Connect a jumper or DC reactor across terminals P-P1.

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.FIN

 

FR-PU04V

H/Sink O/Temp

Indication

 

 

 

 

 

 

 

 

 

 

Name

Fin overheat

 

 

 

Description

If the heatsink overheats, the temperature sensor is actuated to stop the inverter output.

Check for too high ambient temperature.

Check point • Check for heatsink clogging.

Check that the cooling fan is stopped.

Set the ambient temperature to within the specifications.

Corrective action

Replace the cooling fan.

Operation Panel

E.BE

 

FR-PU04V

Br. Cct. Fault

Indication

 

 

 

 

 

 

 

 

 

 

Name

Brake transistor

alarm detection

 

 

 

This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake

Description

transistors.

 

 

 

In this case, the inverter must be powered off immediately.

 

 

 

 

 

• Reduce the load inertia.

 

 

Check point

• Check that the frequency of using the brake is proper.

 

• Check that the brake resistor selected is correct.

 

 

 

 

 

Corrective action

Replace the inverter.

 

 

 

 

 

 

 

Operation Panel

E.GF

 

FR-PU04V

Ground Fault

Indication

 

 

 

 

 

 

 

 

 

 

Name

Output side earth (ground) fault overcurrent protection

Description

This function stops the inverter output if an earth (ground) fault overcurrent flows due to an earth

(ground) fault that occurred in the inverter's output (load) side.

 

 

 

Check point

Check for an earth (ground) fault in the motor and connection cable.

Corrective action

Remedy the earth (ground) fault portion.

 

ERRORS AND PROTECTIVE FUNCTIONS

6

72