Precautions for use of the vector inverter
2.4 Precautions for use of the vector inverter
The
Before starting operation, always recheck the following items.
(1)Use
(2)Power must not be applied to the output terminals (U, V, W) of the inverter. Otherwise the inverter will be damaged.
(3)After wiring, wire
Wire
When drilling mounting holes in a control box or the like, use care not to allow chips etc. to enter the inverter.
(4)Wire the cables of the recommended size to make a voltage drop 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a high frequency.
Refer to page 11 for the recommended wire sizes.
(5)The overall wiring length should be 100m maximum.
Especially for long distance wiring, the
(6)Electromagnetic wave interference
The input/output (main circuit) of the inverter includes harmonic components, which may interfere with the communi- cation devices (such as AM radios) used near the inverter. In this case, install the optional
(7)Do not install a power factor correction capacitor, surge suppressor or radio noise filter
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is installed, immediately remove it. (When the
(8)When rewiring after operation, switch power off, wait for more than 10 minutes, and then make sure that the voltage is zero using a tester, etc. For some time after
(9)A short circuit or earth (ground) fault in the inverter output side may damage the inverter modules.
•Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation resistance may damage the inverter modules.
•Fully check the
(10)Do not use the inverter power supply side magnetic contactor to start/stop the inverter.
Always use the start signal (turn on/off terminals STF,
(11)Across the P and PR terminals, connect only an external regenerative brake discharge resistor. Do not connect a mechanical brake.
(12)Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application (contact) of a voltage higher than the permissible voltage to the inverter I/O signal circuits or oppo- site polarity may damage the I/O devices. Especially check the wiring to prevent the speed setting potentiome- ter from being connected incorrectly to short terminals
(13)Use of
(14)Precautions for use of any motor other than the dedicated motor
a)Vector control cannot be exercised without PLG. b)Connect the PLG directly to the
(15)Since the rated voltage differs from the commercial power supply voltage, the dedicated motor cannot perform commercial power
Motor | Rated Voltage | ||
|
|
| |
3.7kW or less | 170V | ||
|
| ||
5.5kW or more | 160V | ||
| |||
|
|
| |
3.7kW or less | 340V | ||
|
| ||
5.5kW or more | 320V | ||
| |||
|
|
|
21