Biases and gains of speed setting termi- nals (Pr. 902 to Pr. 905, Pr. 917 to Pr. 920)

4.7Biases and gains of speed setting term inals (Pr. 902 to Pr. 905, Pr. 917 to Pr. 920)

Adjust the biases and gains of the speed setting No. 2, torque command No. 3 and multi-function No. 1 terminals.

The "bias" and "gain" functions are designed to adjust the relationship between the 0 to 10V input signal, which is externally input for the setting of output speed, torque or magnetic flux.

Parameter

Name

Factory Setting

Setting Range

Remarks

 

 

 

 

 

 

 

902

Speed setting No. 2 bias

0V

0r/min

0 to 10V

0 to 3600r/min

 

 

 

 

 

 

 

 

903

Speed setting No. 2 gain

10V

1500r/min

0 to 10V

0 to 3600r/min

 

 

 

 

 

 

 

 

904

Torque command No. 3

0V

0%

0 to 10V

0 to 400%

 

bias

 

 

 

 

 

 

 

 

 

 

 

 

 

 

905

Torque command No. 3

10V

150%

0 to 10V

0 to 400%

 

gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

917

No. 1 terminal bias

0V

0r/min

0 to 10V

0 to 3600r/min

Extended mode

(speed)

 

 

 

 

 

 

 

 

 

 

 

 

 

918

No. 1 terminal gain

10V

1500r/min

0 to 10V

0 to 3600r/min

 

(speed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

919

No. 1 terminal bias

0V

0%

0 to 10V

0 to 400%

 

(torque/magnetic flux)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

920

No. 1 terminal gain

10V

150%

0 to 10V

0 to 400%

 

(torque/magnetic flux)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1500r/min)

Output speed

(r/min)

Bias

Pr. 902

0

Factory setting

Gain Pr. 903

-10V

10V

Setting signal

(1500r/min)

Output speed(r/min)

(150%)

Torque (%)

Gain

Bias

Pr. 904 Pr. 919

Pr. 917

Setting signal

10V

Inclination is as set in Pr. 904 (Pr. 917, Pr. 919)

and Pr. 905 (Pr. 918, Pr. 920).

. 905

. 918

. 920

CAUTION

Torque command bias and gain can not be set by applying an external negative setting signal to the torque command No. 3 or No. 1 terminal.

<Setting>

There are the following three methods to adjust the speed setting voltage bias and gain.

1)Method to adjust any point by application of a voltage to across terminals 2(1)(3) - 5

2)Method to adjust any point without application of a voltage to across terminals 2(1)(3) - 5

3)Method that does not adjust the bias voltage

(Example) Pr. 903 "speed setting No. 2 gain"

(Pr. 902 to Pr. 920 can be adjusted in the similar manner.)

<Adjustment procedure> Using the speed setting signal from the operation panel (FR-DU04-1) to make speed setting

(1) Power on (monitoring mode)

 

(2) Choose the PU operation mode.

 

 

 

 

 

 

 

FR-DU04-1

CONTROL PANEL

 

1) Make sure that the inverter is in the PU operation

 

 

mode. (LED of PU is lit.) (Refer to page 28 for mon-

 

 

 

Hz/r

 

 

 

 

 

itor transition.)

 

 

 

 

 

A

 

 

 

 

 

 

V

 

j

 

 

 

MON

EXT

PU

 

Operation mode (PU operation mode)

 

 

REV

FWD

 

FR-DU04-1

 

 

 

 

 

 

 

CONTROL PANEL

 

 

 

 

 

 

 

Hz/r

 

REMARKS

 

 

 

 

A

 

 

 

 

 

V

 

 

 

MON

EXT

PU

 

 

 

 

 

 

ON of the LED is indicated by

, and OFF by .

 

REV

FWD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

47

Page 51
Image 51
Mitsubishi Electronics FR-V500 instruction manual Setting, Output speed, Torque %, 10V, Inclination is as set in Pr Pr , Pr