Easy gain tuning

4.5.5Easy gain tuning-related parameter operation

Refer to the following table for the param eter/gain read/write operation using Pr. 819 "easy gain tuning selection".

 

 

Pr. 819=0

Pr. 819=1

Pr. 819=2

 

 

With inertia estimation, with gain

Inertia as set in Pr. 880, with gain

 

 

Without tuning

 

 

calculation

calculation

 

 

 

 

 

 

 

 

 

Read

Setting is

Inertia estimation result is

Setting is displayed.

 

displayed.

displayed from the RAM.

Pr. 880

 

 

 

 

 

 

 

 

Load inertia estimation result is

 

"load inertia"

 

Setting can be

 

Write

written. (Write is enabled only

Setting can be changed.

 

changed.

 

 

during a stop.)

 

 

 

 

 

 

 

 

 

 

 

 

 

•Every hour after power-on

 

Timing of writing load

 

 

•When the Pr. 819 setting is

When the Pr. 819 setting is

 

 

changed to other than "1".

changed to "2"

inertia ratio and control

Not written

•When the vector control mode is

When Pr. 880 "load ineritia ratio" or

gains into E2PROM

 

 

changed to other drive systems

Pr. 818 "easy gain tuning response

 

 

 

due to the Pr. 800 "control system

level setting" is changed

 

 

 

selection" setting change.

 

 

 

 

 

 

Control gains

Read

Settings are

Gain calculation results (RAM) are

Settings are displayed.

displayed.

displayed.

(Pr. 820, Pr. 821,

 

 

 

 

 

 

 

Settings can be

 

 

Pr. 828, Pr. 422)

Write

Write disabled (operation error)

Write disabled (operation error)

changed.

 

 

 

 

 

 

 

 

 

CAUTION

RAM data is erased when the power is not supplied or the inverter is reset.

45