Mitsubishi Electronics FR-V500 Replacement of parts, Interval, Area Inspection Description

Models: FR-V500

1 112
Download 112 pages 3.61 Kb
Page 99
Image 99

Precautions for maintenance and inspection

 

 

 

Interval

Area of

Inspection

Description

 

Periodic*

 

 

 

Inspection

Item

Daily

year1

years2

 

 

 

 

 

 

 

(1) Check for LED lamp

 

 

 

 

Display

blown.

"

 

 

 

 

(2) Clean.

 

"

 

Display

 

 

 

 

 

 

Meter

Check that reading is

"

 

 

 

normal.

 

 

 

 

 

 

 

 

 

(1) Check for unusual

"

 

 

 

General

vibration and noise.

 

 

 

 

(2) Check for unusual

"

 

 

 

 

 

 

Motor

 

odor.

 

 

 

 

 

 

 

 

 

 

Check with megger

 

 

 

 

Insulation

(across terminals and

 

 

"

 

resistance

earth (ground)

 

 

 

 

 

 

 

 

terminal).

 

 

 

 

 

 

 

 

 

 

Method

Criterion

Instrument

(1)

Lamps indicate

 

 

 

indicator lamps on

(1) Check that lamps

 

 

panel.

are lit.

 

(2)

Clean with rag.

 

 

 

 

Must satisfy

 

Check the readings of

specified and

Voltmeter,

the meters on the panel.

management

ammeter, etc.

 

 

values.

 

(1)

Auditory, sensory,

 

 

 

visual checks.

 

 

(2)

Check for unusual

(1), (2) No fault.

 

 

odor due to

 

 

 

 

 

overheat, damage,

 

 

 

etc.

 

 

Disconnect cables from

 

 

U, V, W (including motor

5Mor more.

500V megger

cables).

 

 

 

 

 

 

Customer’s check

*Values in parentheses indicate those for 400V class. *Consult us for periodic inspection.

6.5.7Replacement of parts

The inverter consists of many electronic parts such as semiconductor devices.

The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.

Part Name

Standard Replacement Interval

Description

 

 

 

Cooling fan

2 to 3 years

Replace (as required)

 

 

 

Main circuit smoothing capacitor

10 years

Replace (as required)

 

 

 

On-board smoothing capacitor

10 years

Replace the board (as required).

 

 

 

Relays

Replace as required.

 

 

 

CAUTION

For parts replacement, consult the nearest Mitsubishi FA Center.

95

Page 99
Image 99
Mitsubishi Electronics FR-V500 instruction manual Replacement of parts, Interval, Area Inspection Description