Basic operation (Speed setting, run, speed meter adjustment)

!External jog operation

Keep the start switch (STF or STR) on to perform operation, and turn it off to stop. 1)Set Pr. 15 "jog speed setting" and Pr. 16 "jog acceleration/deceleration time". 2)Select the external operation mode.

3)Switch on the jog signal. Keep the start switch (STF or STR) on to perform operation. Assign the terminal used for the jog signal in any of Pr. 180 to Pr. 183 and Pr. 187 (input terminal function selection). (Refer to page 61.)

(3)Choosing external/PU combined operation mode 1 (operation using the external start signal and operation panel)

!When setting the start signals from outside inverter (e.g. switches or relays) and the run- ning speed from the operation panel (Pr. 79=3)

•Operation command : start signal connected outside

•Speed setting : of PU or multi-speed command (multi-speed command has priority) For multi-speed command, refer to Pr.4 to Pr.6 on page 50.

Operation

1.Power on Switch power on.

2.Operation mode selection

Set "3" in Pr. 79 "operation mode selection". (Refer to page 52 for details of Pr.79.)

The combined operation mode is selected and the operation status indication "EXT" and "PU" are lit.

3.Start

Turn on the start switch (STF or STR).

The operation status indication "FWD" or "REV" is lit.

REMARKS

• The motor does not start if both the forward and

reverse rotation switches are turned on. If both

switches are turned on during operation, the motor

decelerates to a stop.

• Set the speed in the speed setting mode (Refer to page 27.).

4. Running speed setting

Using

of PU, set the running speed to 150r/min

Display

ON

Flicker

Forward rotation

Reverse

FR-DU04-1

CONTROL PANEL

rotation

 

 

 

Hz/r

 

 

 

 

A

 

 

 

 

V

 

MON

EXT

 

PU

 

 

REV

 

FWD

 

ON

FR-DU04-1CONTROL PANEL

Hz/r

A

3

SET REV FWD

V

and press SET .

The operation command indication FWD or REV is lit.

5. Stop

Turn off the start switch (STF or STR).

The motor decelerates to stop.

The operation status indication "FWD" or "REV" is lit.

MON EXT PU

REV FWD

Forward

FR-DU04-1

CONTROL PANEL

rotation

Reverse

 

Hz/r

 

A

 

rotation

 

V

 

 

 

 

MON EXT

PU

 

 

REV

FWD

OFF

CAUTION

When Pr. 75 "PU stop selection" = "14 to 17",

STOP

RESET is valid.

REMARKS

When setting the start signal from the PU and speed setting signal from outside inverter, set "4" (combined operation mode 2) in Pr.79 "operation mode selection".

RUN AND OPERATION

24

Page 28
Image 28
Mitsubishi Electronics FR-V500 instruction manual External jog operation