Mitsubishi Electronics FR-V500 Control circuit terminal layout, Wiring instructions

Models: FR-V500

1 112
Download 112 pages 3.61 Kb
Page 19
Image 19

Connection diagram, PLG cable, PU connector

Type

Terminal

Terminal Name

 

Description

 

 

Symbol

 

 

 

 

 

 

 

 

 

1 contact output indicating that the output has been stopped by the inverter

 

Contact

 

 

protective function

 

 

 

 

 

 

The terminal function varies with the output terminal function selection (Pr. 195)

 

 

 

 

230VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C (continuity across A-C),

 

 

A, B, C

Alarm output

Normal: continuity across B-C (discontinuity across A-C).

 

 

 

 

setting.

 

 

 

 

 

 

 

Refer to page 61 for details.

 

signalsOutput

 

 

 

 

 

 

 

collectorOpen

DO1 to

Digital output terminals

Permissible load 24VDC 0.1A

 

 

 

DO3

1 to 3

The terminal functions vary with the output terminal function selection (Pr. 190 to Pr.

 

 

192) settings. Refer to page 61 for details.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE

Open collector output

Common terminal for terminals DO1, DO2 and DO3. Isolated from terminals SD and

 

 

common

5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One selected from the monitoring items,

Factory setting of output item:

 

 

DA1

Analog signal output

Speed monitoring, output signal 0 to

 

 

such as the speed, is output.*

 

 

 

 

±10VDC, permissible load current 1mA

 

 

 

 

The output signal is proportional to the

 

 

 

 

 

 

 

 

Analog

 

 

 

Factory setting of output item:

 

 

 

magnitude of the corresponding monitoring

 

DA2

Analog signal output

Torque monitoring, output signal 0 to

 

 

 

item.

 

 

10VDC, permissible load current 1mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog signal output

Common terminal for DA1 and DA2.

 

 

 

5

Isolated from terminals SD and SE.

 

 

 

common

 

 

 

 

Do not earth(ground).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

485-RS

 

 

W ith the PU connector, com m unication can be m ade through RS -485.

 

 

 

 

 

 

 

 

• Conforming standard

: EIA Standard RS-485

 

 

PU connector

• Transmission format

: Multidrop link system

 

 

 

 

• Communication speed : Maximum 19200bps

 

 

 

 

• Overall length

: 500m

 

 

 

 

 

 

 

 

 

* Not output during inverter reset.

REMARKS

For the input terminal function switchover timing, refer to page 42.

(2) Control circuit terminal layout

Terminal screw size : M3.5

Tightening torque : 1.2N·m

When connecting three or more control cables to the No. 5 terminal, connect the accessory No. 5 terminal dedicated L-shaped jumper to the No. 5 terminal.

In this case no cable should be connected to

the screw in the part.

5

A

B

 

C

 

DO1

DO2

DI4

DI3

DI2

DI1

STR

STF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10E

 

2

 

DA1

DO3

 

SE

PZ

 

PZR

PG

RES

PC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

1

 

DA2

PA

 

PAR

 

PB

PBR

SD

OH

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Wiring instructions

1)Terminals 5, SD and SE are common to the I/O signals and isolated from each other. These common terminals must not be connected to each other nor earthed (grounded).

2)Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).

3)Since the control circuit input signals are micro currents, use two parallel micro signal contacts or a twin con- tact to prevent a contact fault.

4)It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals. If the cable gauge used is 1.25mm2 or more, the front cover may be lifted when there are many cables running or the

cables are run improperly, resulting in an operation panel or parameter unit contact fault.

5)The maximum wiring length should be 30m.

15

Page 19
Image 19
Mitsubishi Electronics FR-V500 Control circuit terminal layout, Wiring instructions, Not output during inverter reset