Connection diagram, PLG cable, PU connector

2.2.6Connection to the PU connector

(1)When connecting the operation panel or parameter unit using a connection cable <Recommended connection cable>

Parameter unit connection cable (FR-CB2) (option) or the following connector and cable available on the market

Connector : RJ45 connector

 

 

Example: 5-554720-3 of Tyco Electronics Corporation

Cable

: Cable conforming to EIA568 (e.g. 10BASE-T cable)

 

 

Example: SG LPEV 0.5m m x 4P(twisted pair cable, 4 pairs) of M itsubishi Cable Industries, LTD .

Maximum wiring length : 20m

(2) For computer link communication

Using the PU connector, you can perform communication operation from a personal computer etc. By connecting the PU connector to computers such as a personal computer and FA unit with a communication cable, you can run/ monitor the inverter and read/write parameter values using a user program.

 

Refer to the Instruction Manual (detailed) for details.

 

Conforming Standard

: EIA Standard RS-485

Transmission form

: Multidrop link system

Communication speed : Maximum 19200bps

• Overall length

: 500m

CAUTION

Do not connect the PU connector to the computer's LAN board, FAX modem socket or telephone con- nector. Doing so may damage the inverter due to electrical specification differences.

2.2.7Notes on earthing (grounding)

!Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be earthed

(grounded).

Use the dedicated earth (ground) terminal to earth (ground) the inverter. (Do not use the screw in the case, chassis, etc.)

!Use the largest possible gauge for the earth (ground) cable. The gauge should be equal to or larger than those indicated in the following table. The earthing (grounding) point should be as near as possible to the inverter to minimize the earth (ground) cable length.

Motor Capacity

Earth (Ground) Cable Gauge

200V class

400V class

 

 

 

 

2.2kW or less

2

2

 

 

 

3.7kW

3.5

2

 

 

 

5.5kW, 7.5kW

5.5

3.5

 

 

 

11kW, 15kW

14

8

 

 

 

18.5kW to 37kW

22

14

 

 

 

45kW, 55kW

38

22

 

 

 

!Earth (Ground) the motor on the inverter side using one wire of the 4-core cable.

2

INSTALLATION AND WIRING

18