Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA300SSC / DCA300SSCU Gen. • operation and parts manual — rev. #1 (08/10/11) — page 25

Page 25
Image 25
Multiquip DCA300SSCU manual Load Application, Single Phase Load, Three Phase Load

DCA300SSCU specifications

The Multiquip DCA300SSCU is a powerhouse generator designed for both commercial and industrial applications, providing reliable performance in various environments. With a robust design and advanced technology, this generator stands out in the competitive field of portable power solutions.

One of the main features of the DCA300SSCU is its reliable diesel engine, which provides 300 kVA of power. The generator is powered by a fuel-efficient Yanmar engine, known for its durability and low emissions, making it an eco-friendly choice for users who need sustained power without sacrificing environmental standards. This engine is designed to operate efficiently, ensuring lower operational costs over time.

The DCA300SSCU boasts impressive electrical characteristics. It is equipped with a state-of-the-art automatic voltage regulator (AVR) that ensures voltage stability, protecting sensitive electronic equipment from damage due to voltage fluctuations. Additionally, the generator's output can be customized to meet specific needs, offering versatility for various applications ranging from construction sites to events.

This model integrates advanced noise reduction technology, making it quieter than many traditional generators on the market. An enclosed canopy design significantly dampens noise pollution, an essential feature for operation in urban areas or during nighttime events. This focus on reduced sound output allows for greater flexibility in deployment locations without disturbing nearby environments.

Ease of use and maintenance are other key characteristics of the DCA300SSCU. The generator features a user-friendly control panel that makes operation straightforward, even for individuals with minimal experience. Additionally, the maintenance intervals are designed to be manageable, reducing downtime and ensuring that the generator stays operational when it’s needed most.

In terms of mobility, the DCA300SSCU is designed with a trailer for easy transportation, allowing it to be moved from one job site to another with minimal effort. The robust frame and integrated lifting points ensure stability and safety during transit.

In summary, the Multiquip DCA300SSCU is a powerful, efficient, and versatile generator that meets the demands of numerous applications. With its dependable diesel engine, advanced voltage regulation, noise reduction mechanisms, and user-friendly design, it is an ideal choice for professionals seeking a high-performance power solution.