installation

Connecting the Ground

The nut and ground terminal on the generators should always be used to connect the generators to a suitable ground. The ground cable should be #8 size wire minimum.

At the generator, connect the terminal of the ground cable between the lock washer and the nut (Figure 2) and tighten the nut fully. Connect the other end of the ground cable to a suitable earth ground (ground rod).

GAC-2.2H

120V

 

15A

POWERED by

Honda Engines

211052

GR PRISE DE

TERRE

V 120

AC VOLTMETER VOLTOMETRE CA

OFF

NEUTRAL BONDED TO FRAME

NEUTRE MIS A LA MASSE A LA CARCASSE DU MOTEUR

AC CIRCUIT BREAKER

INTERRUPTEUR DE

COURANT PRINCIPAL

A21210011

 

 

GROUND ROD

 

GROUND

FOR EARTH

 

GROUND

GENERATOR

CABLE

 

GROUND LUG

#8 MINIMUM

 

CONNECT TO

BUILDING

GROUND

IF REQUIRED

8 FT. MINIMUM

REFERENCE

NEC 250-52(C)

Figure 2. Generator Grounding

page 14 — gac2.2H 60 hz gENERATOR• operation and parts manual — rev. #1 (03/31/10)

Page 14
Image 14
Multiquip GAC2.2H manual Installation, Connecting the Ground