LOCATION AND CLEARANCES 5
Provide adequate ventilation and combustion air.
Provide adequate accessibility clearance for servicing and operating the stove.
Never obstruct the front opening of the stove.
GDS28 AND GS28:
As long as clearance to combustibles is kept within the required distances, the most desirable and beneficial lo- cation for a Napoleon stove is in the centre of a building, thereby allowing the most efficient use of the heat created. The location of windows, doors and the traffic flow in the room where the stove is to be located should be consid- ered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist.
22½" |
|
|
| 18½" |
| 5½" | ||||||||
|
|
|
| |||||||||||
11¼" |
|
|
| 4"ø |
| |||||||||
|
|
|
|
| ||||||||||
7"ø AIR |
|
|
|
|
|
|
|
|
|
|
| FLUE |
|
|
INTAKE |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 173/4" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||
15" | 4" | 12" | 10" |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||||||
WINDOW OPENING | 263/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GAS LINE ACCESS HOLE
LOCATED IN PEDESTAL
FIGURE 1BASE
MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES:
FIGURE 2
A. | 7" | D. | 143/4" |
B. | 2" | E. | 4" |
C. | 1"* | F. | 9½" |
NO ADDITIONAL FLOOR PROTECTION IS REQUIRED MINIMUM 20" FROM STOVE TOP TO CEILING
*AT A DISTANCE OF 1" FROM THE WALL, ACCESS TO THE BLOWER SWITCH,
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two sin- gle family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A
Use a firestop when penetrating interior walls, floor or ceil- ing.
DIRECT VENT SPECIFICS - GDS28
VENTING LENGTHS AND AIR TERMI- NAL LOCATIONS
Use only Wolf Steel or Simpson
When using Wolf Steel venting components, use only the following vent kits: WALL TERMINAL KIT GD175
For optimum performance, it is recommended that all horizontal runs have a minimum ¼ inch rise per foot.
These vent kits allow for either horizontal or vertical venting of the stove. FIGURES 3, 4, & 5.
The maximum number of 4" flexible connections is two hori-
zontally or three vertically (ex- cluding the stove and the air
terminal connections).
When terminating vertically, the
minimum vertical rise isFIGURE 3 34 inches above the stove and
the maximum vertical rise is 40 feet.
Deviation from the minimum vertical vent length can create difficulty in burner
Use an adjustable pipe as the final length of rigid pip- ing to the stove for ease of installation.