Napoleon Fireplaces GS 28-P manual 8WALL AND CEILING PROTECTION, Collar, Vent Pipe, Shield

Models: GDS 28-N GDS 28-P GS 28-P GS 28-N

1 24
Download 24 pages 50.96 Kb
Page 8
Image 8
8WALL AND CEILING PROTECTION
This application occurs
FIGURE 11

8WALL AND CEILING PROTECTION

For safe and proper operation of the stove, follow the venting instructions exactly.

HORIZONTAL INSTALLATION: when venting through an exterior wall. FIGURES

4, 5, & 11. Having deter- mined the air terminal lo- cation, cut and frame a hole

in an exterior wall with a minimum square or round opening of 9". (As an alter-

native to framing, a vent pipe shield may be in-

stalled, ensuring a 1" clear- ance to combustibles. See Figure 12.)

For optimum performance, the stove pipe should rise ¼" per foot of run.

1.Mark and cut the vent pipe shield to the determined depth of the combustible wall. Apply a bead of caulking (not supplied) to the framework or to the shield plate (in the case of a finished wall) and secure the shield through the opening to the interior wall. The final location of the vent pipe shield should maintain the required clearance to the 7" vent pipe. Do not fill this cavity with any type of material. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply sealant between the pipe and the firestop spacer.

OR

FIGURE 12

VERTICAL INSTALLATION: This application occurs when venting through a roof. FIGURE 3.

Installation kits for vari-

FIGURE 13

 

ous roof pitches are

 

available from your Na-

 

poleon dealer. See Ac-

 

cessories to order the

 

specific kit required.

 

1.Determine the air terminal location and move the stove into position. Cut and frame 9 inch openings in the ceiling and the roof to provide the minimum 1 inch clearance be- tween the stove pipe and any combustible material. Try to

 

center the exhaust

 

pipe location midway

 

between two joist to

FIGURE 14

prevent having to cut

them. Use a plumb

 

 

bob to line up the

 

center of the open-

 

ings.

DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.

A vent pipe shield will prevent any materials such as insu- lation, from filling up the 1" air space around the pipe. FIGURE 15. Nail headers between the joist for extra sup- port.

2.Apply a bead of caulking (not supplied) to the frame- work or to the Wolf Steel vent pipe shield plate or equiva- lent (in the case of a finished ceiling), and secure over the opening in the ceiling. FIGURE 14. A firestop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. FIGURE 13. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply sealant between the pipe and the firestop

spacer.

VENT

3. In the attic, after the pipe

PIPE

has been installed, slide the

vent pipe collar down to cover

COLLAR

up the open end of the shield

VENT PIPE

and tighten. This will prevent any

SHIELD

materials, such as insulation,

 

from filling up the 1" air space

 

around the pipe.

FIGURE 15

 

W415-0153 / A / 10.29.01

Page 8
Image 8
Napoleon Fireplaces GS 28-P, GDS 28-N, GDS 28-P, GS 28-N 8WALL AND CEILING PROTECTION, Collar, Vent Pipe, Shield