Napoleon Fireplaces GDS 28-P, GS 28-P, GDS 28-N, GS 28-N manual A Bc, first, Figs

Models: GDS 28-N GDS 28-P GS 28-P GS 28-N

1 24
Download 24 pages 50.96 Kb
Page 6
Image 6
A

6 For optimum flame appearance and stove performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.

SPECIAL INSTALLATION EXAMPLE

When a horizontal offset is required in a through-the-roof installation, the following procedure for vent length calcula- tions must be followed:FIGS 5first

The maximum horizontal run is 34 inches with a 90° elbow located 29" above the stove. FIGURE 4.

The maximum horizontal run with a 57 inch vertical rise immediately above the stove is 20 feet . Figures 5.

FIGURE 4

In an installation as shown in FIGURE 7, lengths A and C are known based on room height and roof requirements.

Length C must never be less than 29 inches. Any 90° and 45° elbows must be calculated as 5 feet of venting each.

The allowable horizontal run can be cal- culated using these parameters. In this example, the total vertical height is 20 feet (length "A" is required to be 11 feet while length "C" needs to be 9 feet). The maximum vertical length is 40 feet and all runs and elbows must be subtracted from this maximum vertical length.

A

Manual backgroundBManual background C

FIGURE 7

FIGS 5

The maximum allowable horizontal run that "B" can be is:

40 ft. (maximum vertical run length)

-11 ft. (through the roof vertical rise "A") -10 ft. (2 - 90° elbow)

- 9 ft. (vertical run "C")

10 ft. (maximum allowable horizontal length for "B")

The length of "B" must never be greater than the length of "A" and "C" combined.

OFFSET INSTALLATION EXAMPLE

FIGURE 8

HORIZONTAL RUN NOT TO EXCEED VERTICAL RISE

If vertical rises greater than 57 inches are necessary, the increased rise must be deducted from the maxi- mum horizontal run.

Use chart, Figure 6, to calculate horizontal runs for vertical rises between 29 and 57 inches.

When calculating maximum run lengths, include 10 feet for each 90° elbow or 5 feet for each 45° elbow.

Do not include the first elbow directly off the unit.

R E Q U I R E D

V E R T I C A L

RISE FROM

FIREPLACE

TO FIRST EL-

BOW IN

INCHES

FIGURE 6

CALCULATED HORIZONTAL VENT RUN IN FEET

If a first run of 72 inches is re- quired, using the "First Vent Run" on the chart shows that a maxi- mum second run of 48 inches is allowable.

IF NECESSARY, THE FIRST RUN AND THE SECOND RUN MAY BE REVERSED.

57"

48"

 

second

run

 

 

run

first

 

72"

 

FIGURE 9

W415-0153 / A / 10.29.01

Page 6
Image 6
Napoleon Fireplaces GDS 28-P, GS 28-P, GDS 28-N, GS 28-N manual A Bc, first, Figs