Preparing cables for installation 29

For more information, see Nortel Ethernet Routing Switch 8300 Installation

— Chassis, NN46200-309.

Procedure steps

Step Action

1Add the total (3.3 V and 12 V) input power consumption (wattage) for all components (modules and fan trays or cooling modules).

2Refer to the output power rating of the power supply based on the input connection.

If either the individual or the combined power requirements for the components exceed the power supply rating, you need to add at least another power supply to your configuration.

For the 8005DI DC power supply specifications, see “Model 8005DI DC power supply” (page 47). For the 8005DC power supply specifications, see “Model 8005DC power supply” (page 48)

3Consider your redundant power supply needs. If one power supply satisfies your system power consumption needs, a second power supply provides redundancy. If two power supplies satisfy your system power consumption needs, a third power supply provides redundancy.

--End--

Preparing cables for installation

Prepare the cables for installation of the power supply of the Ethernet Routing Switch 8300.

Nortel does not supply the cables for connecting the DC power supply to the DC input power source. Select cables that comply with the electrical code of the country where you use the DC power supply.

CAUTION

Risk of equipment damage

Make sure that the connection cable used with the DC power supply is appropriate for use with the DC power source to which the power supply connects. Consider gauge, flammability, and mechanical serviceability when you determine which cables to use.