Omega CNI8C, CNI32 Input Type RTD, Rtd Submenu, RTD Types, Rtd Value Submenu, RTD Values, Display

Models: CNI16 CNI32 CNI8DH CNI8C CNI16D CNI8 CNI8DV

1 72
Download 72 pages 49.28 Kb
Page 24
Image 24
Input Type (RTD)

Input Type (RTD)

ENTER INPUT TYPE MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press d 3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is RTD, press a to skip to step 6 (RTD stops flashing).

RTD SUBMENU:

Press b

4)

Scroll through the available selection to RTD (flashing).

Press d

5)

Display shows STRD stored message momentarily and then

 

RTD (not flashing).

 

Press d

6)

Display flashes previous RTD type selection i.e. 392.2

 

(see below for RTD types selection).

 

Press b

7)

Scroll through the available RTD types to the selection of

 

your choice.

 

Press d

8) Display shows STRD stored message momentarily and then

 

advances to RTD RTD value.

 

RTD Types: 392

385

Two, Three or Four-wire

Display:

392.2, 392.3, 392.4, 385.2, 385.3, 385.4

 

Last digit indicates: 2-, 3- or 4-wire input.

RTD VALUE SUBMENU:

Press d 9) Display flashes previous RTD value selection i.e. 100_ (see below for RTD value selection).

Press b 10) Scroll through the available RTD values to the selection of your choice.

Press d 11) Display shows STRD stored message momentarily and then advances to RDG Reading Configuration Menu.

RTD Values:

100 ohm

500 ohm

1000 ohm

Display:

100_

500_

1000

20

Page 24
Image 24
Omega CNI8C, CNI8DV Input Type RTD, Rtd Submenu, RTD Types, Rtd Value Submenu, RTD Values, Enter Input Type Menu, Display