ENTER OUTPUT 1 MENU:

ENTER OUTPUT 1 MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press a 3) Press a, if necessary, until Display advances to OUT1 Output 1 Menu.

Press d 4) Display advances to SELF Self Submenu.

SELF SUBMENU:

The Self Option allows the output of the instrument to be controlled manually from the front panel.

Press d 5) Display flashes the current setting of Self, ENBL Enabled or DSBL Disabled.

Press b 6) Press the b button to select between Enable and Disable. Press d 7) If Self ENBL Enabled was selected, display shows STRD stored message momentarily and then advances to the next

menu (Output 1 setting is completed).

The output is now under the direct control of the operator and can be adjusted in the Run Mode (M00.0 to M99.9), by pressing

the b and c buttons, where M calls for the Manual (Self) Control. For example, setting of M50.0 of an Analog Output of 0 to 10 Vdc would produce roughly 5 Vdc at the output.

8)If Self DSBL Disabled was selected, display shows STRD stored message momentarily and then advances to oPLO Minimum/Percent Low Submenu of Output 1 Menu.

There is a shorter way to Enable or Disable Self Mode. From a Run Mode, press d and then press a. Self Mode is Enabled now. Press b or c to display MXX.X. To disable Self, press d and then press a. Display goes to the Run Mode. Self Mode is Disabled now.

MINIMUM/PERCENT LOW SUBMENU:

Specify in percent, the minimum value (0000) for control output. If the output is analog proportional (Current or Voltage), then the minimum voltage or current, in percent, is specified. If the output is time proportional (Relay, SSR or Pulse), then the minimum duty-cycle, in percent, is specified.

Press d 9) Display flashes 1st digit of previous “Percent Low” setting. Press b & c 10) Use b and c buttons to enter a new value for “Percent Low”. Press d 11) Display shows STRD stored message momentarily and then

advances to oPHI Maximum/Percent High Submenu.