3.2.8 Alarm 2

3.2.8 Alarm 2

This unit is equipped with two physical outputs that can only be configured as follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1

&Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out available only if Analog Output Option board is factory installed.

Alarm must be DISABLED if Ramp is ENABLED.

Figure 3.7 Flow Chart for Alarm 2

ENTER ALARM 2 MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears.

Press d 2) Display advances to INPT Input Menu.

Press a 3) Press a, if necessary, until Display advances to ALR2 Alarm 2 Menu.

Press d 4) Display advances to Alarm 2 ENBL Enable or DSBL Disable Submenu.

ALARM 2 ENABLE/DISABLE SUBMENU:

Press d 5) Display flashes previous selection. Press b until ENBL displays to use Alarm 2.

Press d 6) Display shows STRD stored message momentarily and then advances to ABSo only if it was changed, otherwise press a to advance to ABSo Absolute/Deviation Submenu.

If DSBL Alarm 2 Disabled was selected, all submenus of Alarm 2 will be skipped and meter advances to LOOP Loop Break Time Menu. If ENBL Alarm 2 Enabled was selected, Output 2 will automatically Disabled, and reassigned as Alarm 2.

The remaining Alarm 2 menu items are identical to Alarm 1 Menu. Modifying Alarm Settings will not reset the instrument.