Omega CNI8C PART FACTORY PRESET VALUES .1 Factory preset value, Menu Items, Factory Preset Values

Models: CNI16 CNI32 CNI8DH CNI8C CNI16D CNI8 CNI8DV

1 72
Download 72 pages 49.28 Kb
Page 66
Image 66

PART 5

FACTORY PRESET VALUES

Table 5.1 Factory preset value

MENU ITEMS

FACTORY PRESET VALUES

NOTES

Set Point 1 (SP1)

000.0

 

Set Point 2 (SP2)

000.0

 

Input:

 

 

Input Type (INPT)

TC, type K

 

Reading Configuration (RDG):

 

 

Decimal Point (DEC.P)

FFF.F

 

Temperature unit (TEMP)

°F

 

Filter value (FLTR)

0004

 

Alarm 1 & 2:

 

 

Alarm 1 (ALR1), Alarm 2 (ALR2)

Disable (DSBL)

 

Absolute/Deviation (ABSO/DEV)

Absolute (ABSO)

 

Latch/Unlatch (LTCH/UNLT)

Unlatch (UNLT)

 

Contact Closure (CT.CL)

Normally Open (N.O.)

 

Active (ACTV)

Above (ABOV)

 

Alarm At Power On (A.P.ON)

Disable (DSBL)

Alarm 1 only

Alarm Low (ALR.L)

-100.0

 

Alarm High (ALR.H)

400.0

 

LOOP:

 

 

Loop Break Time (LOOP)

Disable (DSBL)

 

Loop Value (B.TIM)

00:59

 

Reading Adjust Value (R.ADJ)

000.0

 

Setpoint Deviation (SP.dV)

Disable (DSBL)

 

ANALOG OUTPUT (Retransmission)

:

 

Analog Output (ANLG)

Enabled (ENBL)

 

Current/Voltage (CURR/VOLT)

Voltage (VOLT)

 

Scale and Offset

Reading: 0 - 999.9 cts, Output: 0 - 10 V

OUTPUT 1 & 2:

 

 

 

 

 

Self (SELF)

Disabled (DSBL)

Output 1 only

% Low Value (%LO)

0000

Output 1 only

% High Value (%HI)

0099

Output 1 only

Control Type (CTRL)

On/Off

 

Action Type (ACTN)

Reverse (RVRS)

 

Dead Band (DEAD)

020.0

 

PID Auto (AUTO)

Disable (DSBL)

 

Anti Integral (ANTI)

Disable (DSBL)

Output 1 only

Proportion Value (PROP)

020.0

 

Reset Value (REST)

0180

Output 1 only

Rate Value (RATE)

0000

Output 1 only

Cycle Value (CYCL)

0007

 

Damping Factor (DPNG)

0003

 

62