2.4 FRONT OF THE METER (Continued)

MENU Button

In the run mode, press the MENU button to terminate the current measuring process and enter you into the configuration mode.

In the configuration mode, press the MENU button to store changes in the non-volatile memory and then advance you to the next menu item.

To lock the MENU button, install S3E jumper. Refer to Table 3-1 for more information about the S3 jumpers.

RESET Button

In the run mode, press the RESET button to:

*reset the latched setpoints. The display will show "SP.RS" (Setpoint Reset).

*perform tuning for Proportional Control if the meter is setup to serve as a proportional controller (0.3=P refer to Section 4.8.3 and Section 7) the meter will show “TUNE”.

Also in the run mode, if you hard reset or power off/on the meter, it shows "RST" followed by "D.RTD".

In the configuration mode, press the RESET button once to review the previous menu. Pressing the RESET button twice results in a hard reset and returns you to the run mode.

In the setpoint mode, press RESET button to go back to the run mode. THe meter will show “RUN”.