25
3.2.6 Alarm 1
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed.
If Analog Output Option is installed, the controller will skip Alarm 1 Menu
item to Analog Output.
Figure 3.5 Flow Chart for Alarm 1
ENTER ALARM 1 MENU:
Press a1) Press a, if necessary, until CNFG prompt appears.
Press d2) Display advances to INPT Input Menu.
Press a3) Press a, if necessary, until Display advances to ALR1Alarm 1
Menu.
Press d4) Display advances to Alarm 1 ENBL Enable or DSBL Disable
Submenu and flashes the previous selection.
Alarm must be DISABLED
if Ramp is ENABLED.