37
ENTER OUTPUT 1 MENU:
Press a1) Press a, if necessary, until CNFG prompt appears.
Press d2) Display advances to INPT Input Menu.
Press a3) Press a, if necessary, until Display advances to OUT1Output
1 Menu.
Press d4) Display advances to SELF Self Submenu.
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press d5) Display flashes the current setting of Self, ENBL Enabled or
DSBL Disabled.
Press b6) Press the bbutton to select between Enable and Disable.
Press d7) If Self ENBL Enabled was selected, display shows STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
The output is now under the direct control of the operator and
can be adjusted in the Run Mode (M00.0 to M99.9), by pressing
the band cbuttons, where M calls for the Manual (Self)
Control. For example, setting of M50.0 of an Analog Output of 0
to 10 Vdc would produce roughly 5 Vdc at the output.
8) If Self DSBL Disabled was selected, display shows STRD
stored message momentarily and then advances to oPLO
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable Self Mode. From a Run
Mode, press dand then press a. Self Mode is Enabled now. Press bor
cto display MXX.X. To disable Self, press dand then press a. Display
goes to the Run Mode. Self Mode is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press d9) Display flashes 1st digit of previous “Percent Low” setting.
Press b& c10) Use band cbuttons to enter a new value for “Percent Low”.
Press d11) Display shows STRD stored message momentarily and then
advances to oPHI Maximum/Percent High Submenu.