43
3.2.11 Output 2
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.
Figure 3.10 Flow Chart for Output 2
ENTER OUTPUT 2 MENU:
Press a1) Press a, if necessary, until CNFG prompt appears.
Press d2) Display advances to INPT Input Menu.
Press a3) Press a, if necessary, until Display advances to OUT2
Output 2 Menu.
Press d4) Display advances to CTRL Control Type Submenu.
CONTROL TYPE SUBMENU:
Press d3) Display flashes ON.OF ON/OFF, or PIDPID.
Press b4) Scroll through the available selections: “ON/OFF” or “PID”.
Press d5) Display shows STRD stored message momentarily and then
advances to AçTN only, if it was changed, otherwise press ato
advance to AçTN Action Type Submenu.
The ON/OFF control is a coarse way of controlling the Process. The “Dead
Band” improves the cycling associated with the ON/Off control. The PID control
is best for processes where the Setpoint is continuously changing and/or tight
control of the Process Variable is required.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than
Setpoints & Alarms.