Omega Engineering CN 79000 manual End of Secondary Menu when Edit is set to

Models: CN 79000

1 44
Download 44 pages 11.9 Kb
Page 18
Image 18

Power On, PEA2 is reset to the present input. To manually reset the value PEA2 must be in the lower display. Press the ENTER key to reset. PEA2 will be reset and display the present input value.

UAL2 The Valley feature stores the lowest input the Instrument has measured for Zone 2 since the last reset or Power On. At Power On, UAL2 is reset to the present input. To manually reset the value UAL2 must be in the lower display. Press the ENTER key. UAL2 will be reset and display the present input value.

LOrE (Option C 4, Serial Communications) Local / Remote Sta- tus: Select LOC or rE.

LOC The host computer is advised not to send remote commands. Any write commands sent to the controls will be rejected.

rE The host computer is allowed to send write commands.If the control is not addressed within the time set in the nAt (No Activity Timer, see Secure Menu) the CHEC LorE error message will be displayed.

Addr (Option C 4, Serial Communications) Control Address: Set from 1 to 3FF. This number (hexadecimal, base 16) must match the address number used by the host computer. Viewed only in this menu. The value displayed is for Zone

1.The address for Zone 2 is the value for Zone 1 plus one. To change this parameter, see Addr in the Secure Menu.

End of Secondary Menu when Edit is set to 0.