Omega Engineering CN 79000 manual Lrn1 Select YES or no

Models: CN 79000

1 44
Download 44 pages 11.9 Kb
Page 20
Image 20

value of 1 provides an output of one sec- ond on and one second off (50% output). A pulse value of 2 provides an output of one second on and two seconds off (33% out- put). Output at center of band equals one second on, 2(pulse value-1)seconds off.

ProP For Current (Code 5) outputs only.

tun1 Tuning Choice: Select SELF, Pid, SLO, nor, or FASt. SELF The instrument will evaluate the Process and

select the PID values to maintain good control. Active for SP1 only.

Lrn1 Select YES or no

YES Start Learning the Process. After the process has been learned the menu item will revert to no.

no Learning will stay in present mode. dFC1 Damping factor, Select OFF, 1 to 7. Sets the ratio of Rate to Reset for the SELF tunE mode. 7 = most Rate. Factory set to 3. For a fast response process the value should be lowered (less Rate). For a slower pro- cess the value should be increased (more

Rate).

Pid Manually adjust the PID values. PID control con- sists of three basic parameters, Proportional Band (Gain), Reset Time (Integral), and Rate Time (Derivative).

Pb1 Proportional Band (Bandwidth). Select 1 to 9999 °F, °C, or counts.

rES1 Automatic Reset Time. Select OFF, 0.1 to

99.9minutes. Select OFF to switch to OFS1. OFS1 Manual Offset Correction Select OFF, 0.1 to

99.9%. Select OFF to switch to rES1. rtE1 Rate Time. Select OFF, 0.01 to 99.99 min-

utes, Derivative.

SLO PID values are preset for a slow response pro- cess.

nor PID values are preset for a normal response process.

FASt PID values are preset for a fast response process.

ArS1 Anti- Reset Windup Feature: Select On or OFF.

On Reset Offset value will be cleared to 0% when the process input is not within the Proportional Band.

Page 18 of 40

Page 20
Image 20
Omega Engineering CN 79000 manual Lrn1 Select YES or no