InC1 Input Correction: Select -500to 500 °F, °C, or counts. This feature allows the input value to be changed to agree with an external reference or to compensate for sensor error. Note: InC1 is reset to zero when the input type is changed, or when decimal position is changed.

FiL1 Digital Filter: Select OFF, 1 to 99. In some cases the time constant of the sensor, or noise could cause the display to jump enough to be unreadable. A setting of 2 is usually sufficient to provide enough filtering for most cases, (2 represents approximately a 1 second time constant). When the 0.1 degree resolution is selected this should be in- creased to 4. If this value is set too high, controllability will suffer.

LPb1 Loop Break Protection: Select OFF, 1 to 9999 seconds. If, during operation, the output is minimum (0%) or maximum (100%), and the input moves less than 5°F (3°C) or 5 counts over the time set for LPb1, the LOOP bAd message will appear. The loop break error can be reset by pressing the ENTER key when at the LPb1 menu item. The INDEX & ENTER keys may also be used.

If Edit is set to 1, jump to LorE on page 24.

If Edit is set to 3, continue.