The following Menu Items operate on the entire Instrument. There is no Set Point distinction. These items will appear in both the Edit1, Edit2, and Edit3 menus.
SP1o Set Point 1 Output Select: Select OutA or Outb.
OutA Set Point 1 is routed through Output A, Set Point 2 is routed through Output B.
Outb Set Point 1 is routed through Output B, Set Point 2 is routed through Output A.
COPY Copy Zone Parameters. Copies program parameters from one zone to the other.
none No copy function is performed. Factory default. 1to2 Copies all parameters from Zone 1 to Zone 2. 2to1 Copies all parameters from Zone 2 to Zone 1.
Addr (Option C 4, Serial Communications) Control Address: Select from 1 to 3FE. This number (hexadecimal, base 16) must match the address number used by the host computer. The value displayed is for Zone 1. The address for Zone 2 is the value for Zone 1 plus one (e.g. if Addr is set to 17, Zone 1 is assigned to address 17 and Zone 2 is assigned to address
18). Addresses 100, 200, and 300 are reserved for Factory use.
bAUd (Option C 4, Serial Communications) Communication Baud Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number must match the baud rate used by the host computer.
nAt (Option C 4, Serial Communications) No Activity Timer: Set from OFF or 1 to 99 minutes.
1- 99 Maximum time between host computer accesses. If timer counts to 0, CHEC LorE will be displayed.
OFF No Activity Timer function is disabled.