2 Instructions
2-74 CP1E CPU Unit Instructions Reference Manual(W483)
TTIM/TTIMX
Applicable Program Areas
Operands
N: Timer Number

The timer number must be between 0000 to 0255 (decimal).

S: Set Value

TTIM (BCD): #0000 to #9999

TTIMX (Binary): &0 to &65535 (decimal) or #0000 to #FFFF (hex)

Operand Specifications
Flags

Instruction Mnemonic Variations Function

code Function

ACCUMULATIVE TIMER TTIM --- 087 TTIM(087)/TTIMX(555) operates an incrementing

timer with units of 0.1-s.

TTIMX --- 555

Symbol
TTIM TTIMX
BCD Binary
Area Step program areas Subroutines Interrupt tasks
Usage OK OK Not allowed
Operand Description Data type Size
TTIM TTIMX
N Timer Number TIMER TIMER 1
S Set Value WORD UINT 1
Area Word addresses Indirect DM addresses Constants CF Pulse bits TR bits
CIO WR HR AR T C DM @DM *DM
N --- --- --- --- OK --- --- --- --- --- --- --- ---
S OKOKOKOK OKOK OK OK OK
Name Label Operation
Error Flag P_ER ON if in BCD mode and S does not contain BCD data.
OFF in all other cases.
TTIM(087)
N
S
Timer input
Reset input
S: Set value
N: Timer number
TTIMX(555)
N
S
Timer input
Reset input
S: Set value
N: Timer number