Outback Power Systems FX 2024 T installation manual Installation Check List, Mate HUB

Models: FX 2024 T

1 40
Download 40 pages 4.08 Kb
Page 31
Image 31

INSTALLATION CHECK LIST

ITEM

YES

NO

All manuals read and reviewed?

FX

OutBack Charge Controller

MATE

HUB

System mounted with the recommended number and sized fasteners?

System installed according to National Electrical Code (NEC) and local codes?

System inspected?

System permanently grounded?

Did the installer use OutBack recommended wire type and gauge adjusted for temperature ratings and length?

All AC wiring rated for 75° C or higher?

Battery cables rated 75° C or higher?

6 AWG wire used for non-Mobile FX AC Input Hot?

10 AWG or larger wire used for AC HOT OUT?

10 AWG wire or larger used for Mobile FX AC Input Hot?

Non-Mobile FX connected to AC circuit with 60 amp maximum branch-circuit over-current protection?

Mobile FX connected to AC circuit with 30 amp maximum branch-circuit over-current protection?

All cables torqued to OutBack specifications?

AC and PV breakers to 22 inch-lbs?

All DC connections to 10 foot-lbs?

FX AC terminals to 30 inch-lbs?

FX battery breaker to 45 inch-lbs?

All terminal block screws torqued to 2.5 foot-lbs?